- 45 -
⑤
Points. Filter time:
the setting of filter time helps to improve the
smoothness of the signal, the longer the filter time the smoother the signal
but the slower the response.
⑥
Range range:
user-defined range range, divided into upper and lower
limits, can be freely configured. Press [Confirm] to enter "auxiliary
interface" for quick parameter change operation.
⑦
Signal cut:
When the measurement signal is small, the measurement
error is large, especially below 1%, the accuracy will be greatly reduced,
engineering generally do zero processing, that is, cut small flow. When a
certain percentage is set, signals smaller than the range percentage are
forced to be set as the lower limit of the range.
⑧
Linear adjustment:
allow users to adjust the deviation value of the
display value, display data = measurement data * K + B, in general, the
adjustment value should be set to 0.
⑨
Cold end compensation:
When the cursor is in the cold end
compensation setting box, press [Confirm] to switch [given] or [external]
mode, when in the given mode, the cold end compensation value can be
set freely, the cold end compensation value in [external] mode is captured
automatically by the system, and the factory default is [external] mode.
⑩
Flow configuration:
Press [F1] to enter the secondary flow
accumulation parameter setting screen (the minimum accumulation value
is 0, the accumulation value below 0 does not accumulate), the screen
details are shown in the following figure.
⑪
Alarm configuration:
Press [F2] to enter the secondary alarm
configuration interface. The alarm configuration contains parameters such
as alarm threshold, alarm contact, alarm return, etc. The parameters are
described as follows.
A. Alarm threshold: the threshold value generated by the alarm,
the value must be within the range of the channel, the instrument is
divided into four categories: upper limit (HH), upper limit (HI), lower limit