- 72 -
K
should be based on the linear flow meter formula.
Appendix III compensation type and common gas standard density
Appendix 3.1 media compensation type
①
No compensation
When the system does not have temperature and pressure
compensation, the density default is a fixed value of 1.000Kg/m³.
②
General gases
The purpose of compensation for general gases is to convert the
working volume to the volume flow at the standard condition.
The equation of state of a general gas corresponds to the ideal gas
equation of state, and the relationship between the working density
f
and the standard density
n
corresponds to the following
equation
where the standard temperature
T
n
= 20.00°C, the standard pressure
(gauge pressure)
P
n
= 0.000Mpa, and
T
f
is the working condition
temperature,
P
f
P is the working condition pressure (gauge pressure).
③
Saturated Steam
The purpose of saturated steam compensation is to obtain the mass flow
rate.
According to the saturated steam pressure (or temperature) density table
to find the working density, to achieve pressure (or temperature)
compensation. In this case, the density
in the orifice plate of the flow
model is based on the actual input pressure (or temperature) of the
Summary of Contents for HT R71