120
5 Describtion of the counter
or
2.) Set:
reset to P 2
Signal 2 at 0
During unidirectional counting the counter will subtract
Static/dynamic Reset:
Static Reset:
Reset over the entire pulse width of the reset pulse
Dynamic Reset:
Reset via the active edge; thereafter, counter operation is
possible independently of the pulse width of the reset pulse.
Decimal point:
The decimal point is only an optical reading aid on the display and does not change the
value. For example, for a value of 1 pulse per cm, the setting 0,00 makes it easier to read the
value in m and cm.
Input damping
(Attenuation)
The inputs A and B are damped to 60 kHz.
Following maximum input frequencies are not to be exceeded:
Phasediscriminator single evaluation: A and B each 30 kHz (TTL 20 kHz)
Phasediscriminator double evaluation: A and B each 30 kHz (TTL 20 kHz)
Phasediscriminator quadruple evaluation: A and B each 15 kHz (TTL 20 kHz)
Unidirectional counting and directional input: Input A 60 kHz (TTL 20 kHz)
Differential counting, summation (totalizing): Input A + B 60 kHz in total (TTL 20 kHz)
If mechanical contacts are triggered (i.e. relays, switches, Reed contacts, etc.), the input
frequency has to be damped (attenuated) to 30 Hz, so as to filter out bounce pulses.
If damping to 30 Hz is selected, all inputs can be used with 30 Hz.
Summary of Contents for Signo 721.2
Page 2: ......
Page 21: ...21 3 1 Maßblatt Einbau des Multifunktionszählers 3 Aufbau und Bedienung Deutsch ...
Page 23: ...23 VDC 1 Relais 1 Transistor VAC Trafo 1 Relais 1 Transistoren 3 Aufbau und Bedienung Deutsch ...
Page 27: ...27 3 Aufbau und Bedienung Deutsch ...
Page 84: ...84 ...
Page 109: ...109 3 Setup and Operation English ...
Page 166: ......
Page 167: ...Version 1 200712 MG1 ...