Model CFE-415, 427
7
March 2015
An all pole, separate disconnect switch, with proper capacity fuses or
breakers must be installed at a convenient location between the fryer and
the power source, and must be installed according to national and local
codes. It should be an insulated copper conductor rated for 600 volts and
90° C. For runs longer than 50 feet (15.24 m), use the next larger wire
size. CE units require a minimum wire size of 6 mm to be wired to the
terminal block.
It is recommended that a 30 mA rated protective device such as a residual
current circuit breaker (RCCB), or ground fault circuit interrupter
(GFCI), be used on the fryer circuit.
Permanently connected electric fryers with casters must be installed
with flexible conduit and a cable restraint, when installed in the United
States. See illustration at left. Holes are available in the rear fryer frame
for securing the cable restraint to the fryer. The cable restraint does not
prevent the fryer from tipping.
The supply power cords shall be oil-resistant, sheathed flexible cable,
no lighter than ordinary polychloroprene or other equivalent synthetic
elastomer-sheathed cord.
DRYWALL CONSTRUCTION
Secure I-bolt to a building stud. Do
not attach to drywall only. Preferred
installation is approximately six
inches to either side of service.
Cable restraint must be at least six
inches shorter than flexible conduit.
2-6
ELECTRICAL
REQUIREMENTS
(CONT.)