4. Specification 

 
Mains Input 

230 V a.c +10%, -6%  

Frequency 50Hz 
Maximum Input Power 

320VA 

Control Supply Output 

Voltage 28VDC +/- 4%  
(current 5 amps max) 

5/8 volt Supply Output

1

5/8 VDC @ 3 Amps max 

Battery Charger Output 

27.5VDC (adjustable from 22.5V to 29V via 
VR1) temperature compensated (-10°C to +50°C).

Over current protection 

Control Supply: Threshold @ >105% of rated   
                           output current(autorecovery). 
5VDC output

1

: Foldback limited.  

Battery Charger: 2 Amps. 

Fuse Ratings 

Mains: 3.15 Amp Antisurge (T) 5 x 20mm  
Battery: 5 Amps Fast Blow  32mm (1.25”) 

Battery Shut off Voltage 

Less than 18Volts DC 

Common Fault Output 

Open collector output (active high)

2

  

Mains Fault Output 

Open collector output (active high)

3

 
Note 1: The A1584 has a 5VDC output and its associated fault indication, labelled as 5/8V REG. It is possible to obtain an 8VDC 
output by replacing R27 with a 2k7 Ohm 1/4W resistor.  
Note 2: When the respective fault is detected by the A1584 a delay of 3 seconds is initiated and if the fault still exists after this 
delay period the Common Fault output (CF) is activated. 
Note 3: When a fault associated with the Mains input is detected by the A1584 a delay of 2 seconds is initiated and if the fault 
still exists after this delay period the Mains Fault output (MF) is activated. 

 

5. Termination List 

 
BATT+    Battery charger terminal 27.5volts, 2 amps max. two terminals, 2.5mm

2

 cable max. 

 
BATT-     Common 0 volt terminal, two terminals, 2.5mm

2

  cable max. 

 
THERM   Thermistor input, two terminals, 2.5mm

2

  cable max. 

 
Mains (LNE) 2.5mm

2

 cable max. 

  
29VDC INPUT  
 
+               Two terminals, 2.5mm

2

  cable max.   

-                Two terminals, 2.5mm

2

 cable max. 

 
OV           Common O volt output, two terminals, 2.5mm

2

  cable max. 

 
28V          Common 28 volt output @ 5 Amps max, two terminals, 2.5mm

2

 cable max. 

 
5V            Common 5 volt output @ 3 Amp max, two terminals, 2.5mm

2

 cable max. 

 
CF            Power supply Common fault output, open collector, one terminal, 2.5mm

2

 cable max. 

 
MF           Mains Fault output, open collector, one terminal, 2.5mm

2

 cable max. 

 
P               Common pole of the volt-free change over relay, one terminal, 2.5mm

2

 cable max   

C

            Normally closed during fault free condition, open circuit during fault detection, one   

                 terminal, 2.5mm

2

 cable max. 

O              Normally open during fault free condition, closed when fault is detected. One terminal,         
                 2.5mm

2

 cable max. 

NOTE4: Contacts is normally energised 

NOTE5: The volt-free SPCO relay has contacts which are rated to 1A @ 24VDC.

Document Ref: O&M15845T.DOC/Rev 0    22.11.99      Page 5 of 8    Originator KP    Checked By        Approved By

 

 

Summary of Contents for A1584

Page 1: ...cations 6 7 Installation Procedure 7 8 Commissioning 8 1 Introduction Thank you for purchasing this 5A Power Supply Unit This power supply is designed to the requirements of EN54 4 This power supply will provide the user with many years of reliable service NOTE It is important to read this manual before commencing installation Document Ref O M15845T DOC Rev 0 16 11 99 Page 1 of 8 Originator KP Che...

Page 2: ...and other materials can substantially weaken the case WARNING Avoid charging the batteries in float standby applications outside of the range quoted by the battery manufacturer WARNING Do not incinerate batteries If placed in a fire the batteries may rupture with the potential to release hazardous gases and electrolyte VRLA batteries contain substances harmful to the environment Exhausted batterie...

Page 3: ...de power supply whilst the 5VDC output is derived via a regulator on the A1584 controller board In the event of Mains failure the power supply will automatically change over to the standby batteries The power supply has 9 LED status indicators to indicate what type of fault has occurred on the power supply The power supply consists of a steel mounting chassis with the A1584 a switchmode power supp...

Page 4: ...Document Ref O M15845T DOC Rev 0 22 11 99 Page 4 of 8 Originator KP Checked By Approved By ...

Page 5: ...etected by the A1584 a delay of 2 seconds is initiated and if the fault still exists after this delay period the Mains Fault output MF is activated 5 Termination List BATT Battery charger terminal 27 5volts 2 amps max two terminals 2 5mm2 cable max BATT Common 0 volt terminal two terminals 2 5mm2 cable max THERM Thermistor input two terminals 2 5mm2 cable max Mains LNE 2 5mm2 cable max 29VDC INPUT...

Page 6: ...AIN Mains input fault Amber Flashes whenever the DC input from the switchmode unit falls below 28V DC or above 30VDC THERM Thermistor Fault Amber Flashes whenever Thermistor input resistance falls outside its resistance range 800 Ohms to 52kOhms PSU OK PSU Healthy Green Illuminates whenever unit is not displaying any detected faults Turns off whenever charger is checking the presence of the batter...

Page 7: ...nclosure must provide adequate ventilation see battery manufacturer s recommendations The power supply should be mounted on to a metal chassis or back plane using the 4 off M4 x 20mm bolts provided Each of the four bolts should be spaced with the M5 x 6mm spacers provided Figure1 provides information relating to the dimensions and locations of the four fixing holes Earthing Arrangement It is recom...

Page 8: ...not permitted to be used while connected to the power pack otherwise will cause serious damage to internal components 5 As the equipment relies primarily on natural convection for cooling purposes it is important that the enclosure is checked sited in a position with a free flow of air This also applies to equipment fitted with cooling fans 6 Connect the A C mains supply to the mains terminal maki...

Reviews: