6. Adjustments and Indications 

              TABLE 1. Description of Fault Indicators and their functions on the A1584  

 

INDICATOR FUNCTION 

COLOUR

COMMENTS 

PROC 

Processor Fault 

Amber 

Flashes whenever the processor fails to update the 
external hardware watchdog and whenever a 
memory error has been detected by the onboard 
processor.  

BATT 

Battery Fault 

Amber 

Flashes whenever the battery input has a short 
circuit, single battery connected, or battery voltage 
rises above 29.5VDC. 

L/BATT 

Low Battery 
Fault 

Amber Flashes 

whenever 

standby power (battery) falls 

below 19VDC. 

CHARGE 

Charger Fault 

Amber 

Flashes whenever battery is disconnected, battery 
voltage is above intended charge voltage.  

EARTH 

Earth Fault 

Amber 

Flashes whenever a earth fault is detected. 

5/8V 

Regulated 5/8V 
Fault   

Amber 

Flashes whenever 5VDC regulator output is above 
9VDC and below 4VDC. 

MAIN 

Mains input 
fault 

Amber 

Flashes whenever the DC input from the 
switchmode unit falls below 28V DC or above 
30VDC. 

THERM 

Thermistor 
Fault 

Amber 

Flashes whenever Thermistor input resistance falls 
outside its resistance range (800 Ohms to 52kOhms)

PSU OK 

PSU Healthy  

Green 

Illuminates whenever unit is not displaying any 
detected faults. Turns off whenever charger is 
checking the presence of the battery. 

           

                TABLE2. Description of the User Controls and their function on the A1584 

 

User Control 

Designation/Location 

Comments 

EARTH CAP DISABLE 

JP1 

When link is removed the 10uF 
Earth Capacitor is disabled.   

EARTH FAULT DISABLE 

JP2 

When link is removed Earth 
faults are disabled. 

TEST LAMPS PROC FAULT 
RESET 

SW1 

When pressed all the amber 
fault LEDs illuminate except for 
PROC fault. Also clears the 
Memory Checksum Fault Flag 
and clears the PROC Fault LED.

RESET PROC 

SW2 

Resets the on board processor  

VSET 

VR1 

Manual adjustment for Battery 
Charge voltage. 

 

Document Ref: O&M15845T.DOC/Rev 0    22.11.99      Page 6 of 8    Originator KP    Checked By        Approved By

 

 

Summary of Contents for A1584

Page 1: ...cations 6 7 Installation Procedure 7 8 Commissioning 8 1 Introduction Thank you for purchasing this 5A Power Supply Unit This power supply is designed to the requirements of EN54 4 This power supply will provide the user with many years of reliable service NOTE It is important to read this manual before commencing installation Document Ref O M15845T DOC Rev 0 16 11 99 Page 1 of 8 Originator KP Che...

Page 2: ...and other materials can substantially weaken the case WARNING Avoid charging the batteries in float standby applications outside of the range quoted by the battery manufacturer WARNING Do not incinerate batteries If placed in a fire the batteries may rupture with the potential to release hazardous gases and electrolyte VRLA batteries contain substances harmful to the environment Exhausted batterie...

Page 3: ...de power supply whilst the 5VDC output is derived via a regulator on the A1584 controller board In the event of Mains failure the power supply will automatically change over to the standby batteries The power supply has 9 LED status indicators to indicate what type of fault has occurred on the power supply The power supply consists of a steel mounting chassis with the A1584 a switchmode power supp...

Page 4: ...Document Ref O M15845T DOC Rev 0 22 11 99 Page 4 of 8 Originator KP Checked By Approved By ...

Page 5: ...etected by the A1584 a delay of 2 seconds is initiated and if the fault still exists after this delay period the Mains Fault output MF is activated 5 Termination List BATT Battery charger terminal 27 5volts 2 amps max two terminals 2 5mm2 cable max BATT Common 0 volt terminal two terminals 2 5mm2 cable max THERM Thermistor input two terminals 2 5mm2 cable max Mains LNE 2 5mm2 cable max 29VDC INPUT...

Page 6: ...AIN Mains input fault Amber Flashes whenever the DC input from the switchmode unit falls below 28V DC or above 30VDC THERM Thermistor Fault Amber Flashes whenever Thermistor input resistance falls outside its resistance range 800 Ohms to 52kOhms PSU OK PSU Healthy Green Illuminates whenever unit is not displaying any detected faults Turns off whenever charger is checking the presence of the batter...

Page 7: ...nclosure must provide adequate ventilation see battery manufacturer s recommendations The power supply should be mounted on to a metal chassis or back plane using the 4 off M4 x 20mm bolts provided Each of the four bolts should be spaced with the M5 x 6mm spacers provided Figure1 provides information relating to the dimensions and locations of the four fixing holes Earthing Arrangement It is recom...

Page 8: ...not permitted to be used while connected to the power pack otherwise will cause serious damage to internal components 5 As the equipment relies primarily on natural convection for cooling purposes it is important that the enclosure is checked sited in a position with a free flow of air This also applies to equipment fitted with cooling fans 6 Connect the A C mains supply to the mains terminal maki...

Reviews: