I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l
10
www.herrmidifier-hvac.com
Herrtronic
®
Model 6500
Installation Checklist
NOTE:
The HERRMIDIFIER 6500 Humidifier checklist is provided to help the installer ensure a successful installation. If further
assistance is needed from the HERRMIDIFIER representative or the factory, the checklist is expected to be completed. If
a job site visit is required from the HERRMIDIFIER representative or the factory, and the checklist has not been accurately
completed, additional charges may be applied by the individual(s) representing HERRMIDIFIER. If the visit uncovers a
component malfunction, the parts will be replaced under warranty.
_____________________________________________
____________________________________________
Project Name
Checklist completed by
_____________________________________________
____________________________________________
Humidifier Installer (Company)
Checklist completion date
DRAIN RESERVOIR
BALANCE OF DRAIN LINE TO BE 1" MIN. I.D.
DRAIN WATER TEMPERATURE IS SUITABLE FOR PLUMBING.
3/4" MIN. I.D./ 1" MAX. O.D.
FLEXIBLE DRAIN CONNECTION
6" MIN. LENGTH OF 1 1/4" MIN. I.D. VERTICAL COPPER LINE.
IF PVC IS USED, ADD DRAIN TEMPERING.
DURING FILL CYCLE, CHECK TO SEE IF ANY WATER
IS DRAINING FROM UNIT. A LOT OF WATER FLOWING
OUT OF THE UNIT WOULD INDICATE EXCESSIVE
WATER PRESSURE. TURN OFF POWER AND REDUCE
THROUGH METERING FILL SOLENOID OR SUPPLY
VALVE TO HUMIDIFIER. A SMALL AMOUNT OF WATER
IS NOT UNCOMMON.
MAKE SURE ALL HIGH VOLTAGE
ELECTRICAL CONNECTIONS
ARE TIGHT, 15-20 IN-LBS.
POWER SUPPLY:
1. MATCHES DATA PLATE
2. IS PROPERLY GROUNDED
3. CAN CARRY AT LEAST 15 AMPS
4. EXTERNAL FUSED DISCONNECT
PROVIDED BY OTHERS.
SUPPLY WATER (POTABLE)
NO UNTRAPPED LOW SPOT
IN STEAM SUPPLY
AIR FLOW IS HORIZONTAL OR VERTICAL
LOW VOLTAGE TERMINAL STRIP:
1. HUMIDISTAT/HIGH LIMIT HUMIDISTAT
2. AIR PROVING SWITCH
3. 24VAC CONNECTION TO HUMIDISTAT (IF REQ'D)
Figure 10