I n s t a l l a t i o n ,   O p e r a t i o n ,   &   M a i n t e n a n c e   M a n u a l

5

www.herrmidifier-hvac.com

REMOVE THE COVER FROM THE RDU

1.  Loosen the two hex socket head set screws on the fan 

speed control knob and remove knob (Figure 5).

2.  Remove the phillips head screws which fasten the 

cover to the housing.

IV. DIRECT MOUNT OPTION (MDS, MDD)(Figure 6 & 7)

! WARNING!

Be sure to disconnect power to the Herrtronic 

Humidifier before beginning installation.

1.  Assure that the mounting for the Herrtronic unit will 

support the additional 40 pound load of each RDU 

unit.

2.  Remove the knock-out from the top of the Herrtronic 

cabinet and install the 5/16” I.D. plastic bushing for the 

condensate return.

3.  Remove the rearmost 7/8” knockout from the top of  

the Herrtronic cabinet.

4.  Install one 3/4” plasitc bushing from the inside into the 

rearmost 7/8” hole in the bottom of the RDU.

5.  Place the RDU on the Herrtronic cabinet, guiding the 

steam hose(s) into the tank compartment.

6.  Feed the wires (total of seven) through the 3/4” bushing 

and condensate tubing through the 5/16” bushing into 

the Herrtronic unit.

7.  Fasten the RDU in place using four #8-32 self-tapping 

screws installed from inside the Herrtronic cabinet.

8.  Replace the RDU cover & fan speed control knob.

9.  Insert the condensate return tubing into the grey  

plastic fill tee. It will extend I” into the tee.

10. Connect wires # 1 -6 to the 6 pole RDU terminal strip 

located near the top of the Herrtronic high voltage 

electrical compartment. Connect the ground wire #24 

to the Herrtronic ground terminal located near the 

bottom of the high voltage compartment.

NOTE

See Figure 15, 16 & 17 for standard electrical hookup 

for MDM and MDS. 

11.  Remove jumper wire #39 from the Herrtronic 12 

pole controls terminal strip located in the low voltage 

electrical compartment between poles #1 and #2.

Installation is now complete. Proceed to the RDU Operation

section of this manual then to the Start-Up section of the

Herrtronic Installation and Operation Manual OM-93.

Figure 6 - MDS Direct Mount

Figure 7 - MDD Direct Mount

ENTER

FAULTS

HERRTRONIC MD

ON/OFF

CYL FULL

BACK

FAULT

POWER

HERRMIDIFIER

HERRMIDIFIER

HERRMIDIFIER

HERRMIDIFIER

HERRMIDIFIER

SLAVE

FAULT

POWER

BACK

ENTER

FAULTS

ON/OFF

CYL FULL

MASTER

FAULT

POWER

BACK

ENTER

ON/OFF

FAULTS

CYL FULL

HERRTRONIC MD

PHILLIPS HEAD SCREWS

    (6) PER SIDE

    (1) ON FRONT SIDE

Fan Speed Control Knob

Figure 5

Summary of Contents for Herrtronic RDU-D

Page 1: ...Engineered Humidification Systems H e r r m i d i f i e r w w w h e r r m i d i f i e r h v a c c o m Herrtronic RDU D Supplemental Manual...

Page 2: ...ns 4 III Installation Preparation 4 Unit Clearances 4 IV Direct Mount Option 5 MDS with Direct Mount RDU 5 MDD with Direct Mount RDU 5 V Remote Mount Option 6 MDS with Remote RDU 6 MDD with Remote RDU...

Page 3: ...NCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FORPARTICULAR PURPOSE The foregoing shall constitute the total liability of seller in the case of defective performance of all or any of the...

Page 4: ...igure 2 Overall Dimensions III INSTALLATION PREPARATION WARNING Disconnect power to the humidifier while installing RDU The RDU unit must either be placed higher than the Herrtronic unit or provisions...

Page 5: ...nto the Herrtronic unit 7 Fasten the RDU in place using four 8 32 self tapping screws installed from inside the Herrtronic cabinet 8 Replace the RDU cover fan speed control knob 9 Insert the condensat...

Page 6: ...low spots the length should be trimmed so that it can extend 1 into the grey plastic fill tee in the Herrtronic unit 12 National state or local electrical codes may require the use of two separate co...

Page 7: ...horizontally and vertically by adjusting the louvers on the air discharge grille Louvers adjusted as shown in Figure 12 produce the most consistent and shortest evaporation distance Figure 12 Louver D...

Page 8: ...2 Check fuses in RDU 3 Check wiring to fan 4 Check voltage to fan should be 220 VAC 10 5 Replace fan and capacitor Fan speed adjustment not working 1 Replace rheostat Water spitting out of manifold 1...

Page 9: ...er RDU D 1T 2T for 380 EST 1416 Fuseholder DH 052 Foam Tape EST 1417 Fuse 1 A EST 230 Steam Hose EST 1447 1 EST 1447 2 Manifold Assembly Specify Unit Model Number EST 353 Bushing EST 531 5 Pole Termin...

Page 10: ...ronic RDU D Supplement I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 10 www herrmidifier hvac com H2 FOR 460V INPUT H3 FOR 600V INPUT Figure 15 RDU D with 460 600V Transf...

Page 11: ...Herrtronic RDU D Supplement I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 11 www herrmidifier hvac com Figure 16 RDU D with 380V Transformer...

Page 12: ...Herrtronic RDU D Supplement I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 12 www herrmidifier hvac com Figure 17 RDU D w o Transformer...

Page 13: ...terminal of the differential pressure switch in the RDU D unit number 2 Remove the spade connector and cap with a wire nut 2 Disconnect Blue wire number 5 from terminal strip number 1 on RDU D unit n...

Page 14: ...d Humidification Systems Form No OM 102 09 13 Herrmidifier 2013 All Rights Reserved Herrmidifier 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www herrmidifier hvac com cs herrmidifier...

Reviews: