V. REMOTE MOUNT OPTION (MDM, MDS, MDD)

1.  The RDU may hang directly on a wall using the two  

1/4” x 2” lag screws included. There are two key-hole 

slots on the back of the cabinet which engage these 

screws. Be certain that: 1) the screws are fastened 

securely enough to the wall to support the 40 lbs. 

weight of each RDU unit, and 2) the screws are level. 

Turn the screws in until the heads are 1/8” away from 

the mounting surface.

2.  Hang the unit on the wall and tighten the two lag 

screws.

3.  The steam hose(s) is to be connected using the steam 

inlet union(s) (Figure 8).

4.  Trim the steam hose(s) which is connected to the RDU 

manifold so that it fits properly onto the union(s) and   

secure connections with a hose clamp(s).

5.  Fasten steam inlet union(s) to bottom or back of RDU 

cabinet with screws.

6.  Remove the knockout from the top of the Herrtronic 

cabinet and install the 5/16” I.D. plastic bushing 

(included).

7.  Remove the 18” piece of condensate return tubing 

connected to the manifold elbow.

8.  Uncoil the 10’ piece of condensate return tubing (drain 

line), feed into the RDU cabinet, from the bottom or  

back, and connect to the manifold elbow.

9.  Run the condensate return tubing down into the 

Herrtronic cabinet through the 5/16” I.D. plastic 

bushing.

10. The condensate tubing can be attached to the steam 

hose or electrical conduit interconnecting the RDU 

and Herrtronic with cable ties or equivalent.

11.  After the condensate tubing is secured, insuring that 

there are no kinks or low spots, the length should be 

trimmed so that it can extend 1” into the grey plastic fill 

tee in the Herrtronic unit.

12. National, state or local electrical codes may require 

the use of two separate conduits - one for high voltage 

supply power and one for control wiring.

13. There are a total of seven wires which are to be 

connected between the RDU and the Herrtronic unit. 

The RDU receives all of its power and control from the 

Herrtronic unit. Use the two 7/8” holes or knockouts 

on the bottom or back of the RDU cabinet and the two 

7/8” knockouts on the top of the Herrtronic cabinet for 

wiring conduit.

14. Wires #3 and #4 are the high voltage power supply 

and should be run in one conduit.

15. Along with the ground wire #24, wires #1, #2, #5, and 

#6 should be run in the second conduit.

16. Connect wires # 1-6 to the 6 pole RDU terminal strip 

located near the top of the Herrtronic high voltage 

electrical compartment. Connect the ground wire #24 

to the Herrtronic ground terminal located near the 

bottom of the high voltage compartment.

NOTE

See Figure 15, 16 & 17 for standard electrical hookup 

for MDM and MDS.

17. Remove jumper wire #39 from the Herrtronic 12 

pole controls terminal strip located in the low voltage 

electrical compartment between poles #1 and #2.

18. Replace the RDU cover and the fan speed control 

knob.

Installation is now complete. Proceed to the RDU operation 

section then to the start-up section of the Herrtronic 

Installation, Operations and Service Manual OM-93.

Figure 8 - Steam Connections (Side View)

Figure 9 - Drain Line (Front View)

Figure 10 - MDS Remote Mount

BLOWER

DRAIN

LINE

STEAM HOSE

STEAM INLET UNION

 (REMOTE MOUNT)

STEAM INLET UNION
(ALTERNATE LOCATION)

DRAIN

LINE

GRILL

>50 lb/hr requires second hose

CYL FULL

POWER

FAULT

BACK

ON/OFF

FAULTS

ENTER

HERRTRONIC MD

Figure 10 - Front View

Summary of Contents for Herrtronic RDU-D

Page 1: ...Engineered Humidification Systems H e r r m i d i f i e r w w w h e r r m i d i f i e r h v a c c o m Herrtronic RDU D Supplemental Manual...

Page 2: ...ns 4 III Installation Preparation 4 Unit Clearances 4 IV Direct Mount Option 5 MDS with Direct Mount RDU 5 MDD with Direct Mount RDU 5 V Remote Mount Option 6 MDS with Remote RDU 6 MDD with Remote RDU...

Page 3: ...NCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FORPARTICULAR PURPOSE The foregoing shall constitute the total liability of seller in the case of defective performance of all or any of the...

Page 4: ...igure 2 Overall Dimensions III INSTALLATION PREPARATION WARNING Disconnect power to the humidifier while installing RDU The RDU unit must either be placed higher than the Herrtronic unit or provisions...

Page 5: ...nto the Herrtronic unit 7 Fasten the RDU in place using four 8 32 self tapping screws installed from inside the Herrtronic cabinet 8 Replace the RDU cover fan speed control knob 9 Insert the condensat...

Page 6: ...low spots the length should be trimmed so that it can extend 1 into the grey plastic fill tee in the Herrtronic unit 12 National state or local electrical codes may require the use of two separate co...

Page 7: ...horizontally and vertically by adjusting the louvers on the air discharge grille Louvers adjusted as shown in Figure 12 produce the most consistent and shortest evaporation distance Figure 12 Louver D...

Page 8: ...2 Check fuses in RDU 3 Check wiring to fan 4 Check voltage to fan should be 220 VAC 10 5 Replace fan and capacitor Fan speed adjustment not working 1 Replace rheostat Water spitting out of manifold 1...

Page 9: ...er RDU D 1T 2T for 380 EST 1416 Fuseholder DH 052 Foam Tape EST 1417 Fuse 1 A EST 230 Steam Hose EST 1447 1 EST 1447 2 Manifold Assembly Specify Unit Model Number EST 353 Bushing EST 531 5 Pole Termin...

Page 10: ...ronic RDU D Supplement I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 10 www herrmidifier hvac com H2 FOR 460V INPUT H3 FOR 600V INPUT Figure 15 RDU D with 460 600V Transf...

Page 11: ...Herrtronic RDU D Supplement I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 11 www herrmidifier hvac com Figure 16 RDU D with 380V Transformer...

Page 12: ...Herrtronic RDU D Supplement I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 12 www herrmidifier hvac com Figure 17 RDU D w o Transformer...

Page 13: ...terminal of the differential pressure switch in the RDU D unit number 2 Remove the spade connector and cap with a wire nut 2 Disconnect Blue wire number 5 from terminal strip number 1 on RDU D unit n...

Page 14: ...d Humidification Systems Form No OM 102 09 13 Herrmidifier 2013 All Rights Reserved Herrmidifier 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www herrmidifier hvac com cs herrmidifier...

Reviews: