9
Menu navigation and adjustment values
52
9.12.10
External requirement
The external requirement module provides an interface to an external foreign control loop (e.g. central
building control system). The requirement, which can be digital or analogue, is registered as a required
temperature (e.g. boiler must temperature by the boiler or buffer top temperature by the buffer) in the heat
supplier (e.g. boiler or buffer).
Navigation:
→
→
External requirement
Screen:
By pressing the button:
the „external requirement status“ menu will be displayed
the menu for the "settings" will be displayed
the „requirement curve“ menu will be displayed
the „barrier times“ menu will be displayed
External requirement
Indicates a digital input signal of the external control loop (requirement):
If the indicator lamp lights up, the external control loop sends a requirement to
the digital input.
Term
Description
Unit
Menu "Status"
Status 1
1
Demand active
Indicates the state of the external demand
-
Menu "Settings"
Settings
1
External must
temperature
Setting up the (digital) external set temperature (50-100):
The boiler will operate with the external set temperature (fixed) as long as
the analogue set temperature does not exceed the setup temperature
°C
Menu "Requirement curve"
Requirement curve
1
Summary of Contents for BioFire 1000
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system BioFire 500 600 800 1000 1250 1500 ...
Page 89: ...Annex 14 89 14 ANNEX 14 1 Additional boiler module Hydraulic recommendation 1 ...
Page 90: ...14 Annex 90 Hydraulic recommendation 2 ...
Page 91: ...Annex 14 91 14 2 Solar module Program 1 ...
Page 92: ...14 Annex 92 Program 2 ...
Page 93: ...Annex 14 93 Program 3 ...
Page 94: ...14 Annex 94 Program 4 ...
Page 95: ...Annex 14 95 Program 5 ...
Page 96: ...14 Annex 96 Program 6 ...
Page 97: ...Notes 15 97 15 NOTES ...