3
Fuels
8
Fuel variability
: In order to ensure the stability of the
combustion and power output of the boiler, a gradual
change in the fuel (heating value Hu, sizes, density,
water content) is accepted, which does not exceed 10%
of each value mentioned in less than 30 minutes.
3.4
Unsuitable fuels
The burning of unsuitable fuels could lead to
uncontrolled combustion. Operational faults and
consequential damage are likely to occur.
Possible consequential damage:
−
Damage to the thermodynamic combustion chamber,
the lambda probe, the flue gas sensor and the
combustion chamber sensor due to aggressive
residues in the boiler
−
Sooting or corrosion in the filling area due to
condensation as a result of using fuel that is too
moist.
−
The escape of flue gas from the airflow apertures
through uncontrolled combustion (deflagrations).
3.5
Fuel change
If you use a different fuel type as specified mind:
•
allowed fuels (see clean air act)
•
Water content and the fuel size are in
admissible range.
•
it is eventually necessary the adjustment of
the blower engine speed and fuel level
adjustments
to
tune
new.
Summary of Contents for BioFire 1000
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system BioFire 500 600 800 1000 1250 1500 ...
Page 89: ...Annex 14 89 14 ANNEX 14 1 Additional boiler module Hydraulic recommendation 1 ...
Page 90: ...14 Annex 90 Hydraulic recommendation 2 ...
Page 91: ...Annex 14 91 14 2 Solar module Program 1 ...
Page 92: ...14 Annex 92 Program 2 ...
Page 93: ...Annex 14 93 Program 3 ...
Page 94: ...14 Annex 94 Program 4 ...
Page 95: ...Annex 14 95 Program 5 ...
Page 96: ...14 Annex 96 Program 6 ...
Page 97: ...Notes 15 97 15 NOTES ...