Fault Reports and their correction
56
Betriebsanleitung_firematic_20-301_Touch_Englisch V1.2
Fault reporting on the display
Possible cause?
Suggestions for rectifying
F: GRATE CLEANING 3
Fault when closing the BFP
damper
•
Contact
your
specialist
installer.
FAULT 84
F: SUCTION MODE
Fault in pellet feed system
Pellet store empty
Vacutrans valve out of position
Vacutrans valve gasket defective
Leak in pellet feed hose
Suction air hose leaking or loose
Suction turbine defective
•
Check the fill level of the
pellet store and top up if
necessary.
•
Contact
your
specialist
installer, falls der Füllstand
des Pelletlagers ausreichend
ist und der Fehler immer
noch auftritt
FAULT 85
F: SUCTION VALVE
Fault in the Vacutrans damper
Vacutrans damper out of position
Sensor out of position
•
Contact
your
specialist
installer.
FAULT 86
F: ASH CONTAINER
Ash container door open
•
Contact
your
specialist
installer.
FAULT 87
F: NIVEAU COMPACT
Niveau container at the compact
container empty
•
Control container level
FAULT 88
F: NIVEAU SUCTION
Niveau container at the suction
container empty
•
Control container level
FAULT 89
F: COMB. ROOM SENSOR
Endswitch of the combustion
room door has been activated –
Combustion chamber door is
open
•
Close combustion chamber
door
•
Control endswitch
FAULT 90
F: WARNING ASH DISCHARGE
Ash discharge has not been
cleaned or does not rotate
•
Ash container is full
•
Foreign bodies are blocking
the screw
•
Motor is defect
•
Empty the ash container
•
Remove foreign bodies
•
Replace the motor
FAULT 91
F: ERROR ASH DISCHARGE
Ash discharge has not cleaned
for several times -> system turns
off
•
Ash container is full
•
Foreign bodies are blocking
the screw
•
Motor is defect
•
Empty the ash container
•
Remove foreign bodies
•
Replace the motor
FAULT 92
F: ENDSW. ROOM DISCHARGE
Endswitch room discharge has
been activated
•
Receipt motor protection
•
Remove foreign bodies
•
Use an other fuel
•
Replace the motor
•
Renew the screw
FAULT 93