8
Temperature manager
16
If there is no buffer in the system, then the MUST-temperature from the individual modules is determined and
to that an adjustable temp. increase is added. The highest of these temperatures is the boiler-MUST-
temperature. To this an adjustable hysteresis is added and the result is the boiler-END-temperature (see fig.
8.4). Caution: Consider the set minimum requirement.
Fig 8.4: Example temperature manager when operation without buffer
If a time mode is applied directly on the buffer, then the required buffer-top-temperature is set directly in the
time mode module. Now it must be distinguished again if the buffer-top-temperature is higher than the
adjusted buffer-bottom-MUST-temperature. In this case the required boiler temperature is the result of the
required buffer-bottom-MUST-tempe the adjusted temp. in the adjusted difference (see fig.
8.5). If this is not the case, the required boiler temperature is the result of the required temperature + the
adjusted temp. increase (see fig. 8.6). Caution: Consider the set minimum requirement.
Fig 8.5: Example temperature manager when time mode with difference
Summary of Contents for firematic CONDENSATION 30
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic CONDENSATION 30 40 ...
Page 83: ...Annex 15 83 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 84: ...15 Annex 84 Hydraulic recommendation 2 ...
Page 85: ...Annex 15 85 15 2 Solar module Program 1 ...
Page 86: ...15 Annex 86 Program 2 ...
Page 87: ...Annex 15 87 Program 3 ...
Page 88: ...15 Annex 88 Program 4 ...
Page 89: ...Annex 15 89 Program 5 ...
Page 90: ...15 Annex 90 Program 6 ...
Page 91: ...Notes 16 91 16 NOTES ...