Fault reports and their corrections
10
69
No. Fault report
Cause of fault
Fault correction
058
CHECK DATA BOILER
Setting value is not within the valid
range when switching on the boiler
Restart T-Control
Check boiler parameter
059
CAN-ID
used CAN-ID must not be used
change station number of the modul
060
INSERTION IN ACTION
Stoker temperature in operation or
during the ignition phase rises
above 70 °C
Check fuel quality
Check fuel storage room (fuel level)
Clean intermediate hopper level
sensor
061
INSERTION NOT IN
ACTION
Stoker temperature not in action or
during the ignition phase rises
above 70 °C
Chimney draught to high
Feeding channel leakage
Check fuel quality
Shortening burn out time
Underrun minimum running time
062
INSERTION BACKFIRE
Stoker temperature within 30 min.
not under 70°C
Chimney draught to high
Boiler system leakage
Check fuel quality
Shortening burn out time
Underrun minimum running time
✆
- contracting party
063
OPEN BFP
BFP-Open-Contact is not reached
during activation
Check fuel quality
Clean intermediate hopper level
sensor
Check drive arm
✆
- contracting party
064
CLOSE BFP
BFP-Open-Contact is not reached
during activation
Check fuel quality
Clean intermediate hopper level
sensor
Check drive arm
✆
- contracting party
065
CONTACTS BFP
BFP open and BFP closed contact
active at the same time
✆
- contracting party
Carry out check BFP by specialist
personnel
066
IGNITION
no successful ignition detected after
the ignition time has elapsed
Check fuel level
Check burning parameters, adjust
as adapt
Check fuel level during firing
Check ignition element
067
FIRE OUT
no successful ignition detected after
the ignition time has elapsed
Check fuel level
Check burning parameters, adjust
as adapt
Clean intermediate hopper level
sensor
068
TEMP. CONTROL
Fuel storage room temperature
sensor has exceeded the maximum
permissible temperature
Check fuel storage room
Alarm fire brigade in case of fire
069
STL
Boiler temperature has exceeded
the maximum permissible boiler
temperature
Cool down boiler (< 75 °C)
Quit STL
070
LAMBDA FUEL
Material correction of the lambda
control has been at the upper or
lower limit for 30 minutes
Adjust fuel values
✆
- contracting party
071
LAMBDA PROBE
Lambda probe value does not
change
clean lambda probe
✆
- contracting party
Summary of Contents for firematic CONDENSATION 30
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic CONDENSATION 30 40 ...
Page 83: ...Annex 15 83 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 84: ...15 Annex 84 Hydraulic recommendation 2 ...
Page 85: ...Annex 15 85 15 2 Solar module Program 1 ...
Page 86: ...15 Annex 86 Program 2 ...
Page 87: ...Annex 15 87 Program 3 ...
Page 88: ...15 Annex 88 Program 4 ...
Page 89: ...Annex 15 89 Program 5 ...
Page 90: ...15 Annex 90 Program 6 ...
Page 91: ...Notes 16 91 16 NOTES ...