Maintenance schedule
11
77
11.3
Biannual inspection
Item
Procedure
ID-fan
Function test of ID-fan using the aggregate
test
Check ID-Fan for abnormal or conspicuous
running noises
Light barrier
system (symbolic
representation)
Unscrew revision cover (depending on the
boiler type)
Clean
sensors
on
the
inside
of
the
intermediate hopper with soft tissue on the left
and right
Heat exchanger
Demount top boiler cover (1)
Unscrew
and
remove
heat
exchanger
insulation cover (2)
Remove deposit and check heat exchanger
visually for damages and wear.
Conduct function test of heat exchanger using
the aggregate test
Siphon
Clean or flush siphon
Ignition pipe
Clean from the back with cleaning brush