9
T-CONTROL
36
Term
Description
Unit
Boiler run time
Displays the boiler run time (=sum of nominal load-, modulation-, part
load- and burn down- /burn out phase)
h
Total
Display of the total operation hours of the system
(incl. Ready)
h
Total generated energy Display of the total energy generated by the system
kWh
Operating hours 2
1
2
Operating hours until
inspection
Display Operating hours until inspection. Can be reset by entering a code.
Information message "Maintenance" (error No.38) appears after the set
inspection interval has been exceeded (standard: 1000 operating hours).
h
Maintenance interval
date:
Display date until to next maintenance.
Information message "Service" (Error No. 39 ) appears after exceeding
the set maintenance interval (standard: 3000 operating hours) or after
exceeding the annual interval.
-
Maintenance interval
rest - operating hours:
Display rest-operating hours until to next maintenance
h
Interval ash tray
Anzeige des Intervalls (Entleeren) der Aschenlade
h
pellet sucker
*only at Suction discharge
Display rest-operating hours until to next maintenance of pellet sucker.
h
ignition fan*
Display rest - operating hours of the ignition fan until to next maintenance
of ignition fan.
h
Summary of Contents for firematic PELLET 120
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic PELLET 120 201 ...
Page 84: ...15 Annex 84 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 85: ...Annex 15 85 Hydraulic recommendation 2 ...
Page 86: ...15 Annex 86 15 2 Solar module Program 1 ...
Page 87: ...Annex 15 87 Program 2 ...
Page 88: ...15 Annex 88 Program 3 ...
Page 89: ...Annex 15 89 Program 4 ...
Page 90: ...15 Annex 90 Program 5 ...
Page 91: ...Annex 15 91 Program 6 ...
Page 92: ...16 Notes 92 16 NOTES ...
Page 93: ...Notes 16 93 ...