10
Fault reports and their corrections
70
No. Fault report
Cause of fault
Fault correction
026
OVERHEAT
boiler temp. higher 98°C or. 108°C
▪
Check settings
▪
Check back flow mixer
▪
Check back flow pump
027
SOLAR OVERHEATING
Fault is shown, if collector
temperature exceeds 140°C
▪
Check solar pump
▪
Check solar tank level
028
SOLAR MAX. LOADING
collector temperature exceeds 120
°C
▪
Check solar pump
▪
Check solar tank level
029
ANTIFREEZE BOILER
Boiler temperature respectively
operation room temperature under 7
°C
Check or increase the room
temperature in the boiler room.
030
ANTIFREEZE BUFFER
Buffer bottom sensor temperature
under 7 °C
Check or increase the room
temperature in the boiler room.
031
ANTIFREEZE HOT
WATER TANK
Hot water tank under 7 °C
Check or increase the room
temperature in the boiler room.
032
ANTIFREEZE HEATING
CIRCUIT
Flow or return sensor below 7 ° C;
Room temp. sensor below 5 ° C
Check or increase the room
temperature in the boiler room.
033
ANTIFREEZE SOLAR
Collector temperature under set up
antifreeze temperature
-
034
ANTIFREEZE MODULE
Sensor value below 7 °C
-
036
ANTIFR. ADD. BOILER
Sensor value below 7°C
-
037
HOT WATER TANK
LOADING
Hot water tank didn´t reach set
temperature during loading time; hot
water tank loading gets blocked till
fault correction
▪
Adapt loading time
▪
Activate hot water tank priority
▪
Hot water tank settings (min./
must)
038
Inspection
when exceeding the set inspection
interval
▪
Conduct maintenance according
to maintenance schedule
▪
Fault has to be receipted
manually
▪
inspection intervals -> RESET
039
SERVICE
This fault text occurs after 3000
operating hours
Carry out boiler system
maintenance by authorised
personnel
040
OVERHEAT ADD.BOILER
This fault text occurs if additional
boiler temperature exceeds 92 °C
-
041
HEATING OFF
Boiler operation mode “HEATING
OFF” is activated
-
042
BLOCKING
PROTECTION
Blocking protection is active
-
043
TIMEOUT ADD. BOILER
Additional boiler minimum flue gas
temperature wasn´t reached within
1 hour (operation mode:
automatic/burner)
▪
Check additional boiler
044
LEGIONELLA
PROTECTION.
Tank thermal disinfection active;
Tank will be heated up to 75°C
-
045
CHIMNEY SWEEP.
MODE
when starting Chimney clean mode
(see chapter CHIMNEY SWEEP.
MODE)
046
MOD.ERR EXT.
if CAN communication to the
external module is interrupted
▪
Check module CAN connection
▪
Check module
▪
✆
- contracting party
047
MOD.ERR INT.
if CAN communication to the
external module is interrupted
▪
Check module CAN connection
▪
Check module
▪
✆
- contracting party
Summary of Contents for firematic PELLET 120
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic PELLET 120 201 ...
Page 84: ...15 Annex 84 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 85: ...Annex 15 85 Hydraulic recommendation 2 ...
Page 86: ...15 Annex 86 15 2 Solar module Program 1 ...
Page 87: ...Annex 15 87 Program 2 ...
Page 88: ...15 Annex 88 Program 3 ...
Page 89: ...Annex 15 89 Program 4 ...
Page 90: ...15 Annex 90 Program 5 ...
Page 91: ...Annex 15 91 Program 6 ...
Page 92: ...16 Notes 92 16 NOTES ...
Page 93: ...Notes 16 93 ...