Fault reports and their corrections
10
71
No. Fault report
Cause of fault
Fault correction
048
MOD.ERR BOILER
if CAN communication to the power
unit is interrupted
▪
Check module CAN connection
▪
Check module
▪
✆
- contracting party
049
DATAERROR MEMORY
EXTERNAL
Data adjustment error at external
module
✆
- contracting party
050
DATAERROR MEMORY
INTERNAL
Data adjustment error at external
module
✆
- contracting party
051
DATAERROR MEMORY
BOILER
in the event of an error in the
adjustment data of the power unit
(when starting the system)
✆
- contracting party
053
ADDITIONAL FLUE GAS
SENSOR
Additional boiler flue gas
temperature out of range
▪
Check sensor, replace
asnecessary
▪
Check plug, replace asnecessary
▪
Check wiring incl. connections,
replace asnecessary
054
EXTERNAL SET POINT
Signal less than 1.2 volts and valid
signal was already present
▪
Check external (additional) control
signal
▪
Check plug, replace asnecessary
▪
Check wiring incl. connections,
replace asnecessary
055
BACK FLOW SET
if the Backflow-temperature in
operation does not exceed 53 ° C
within 2 hours
▪
Function check mixer with mixer
motor
▪
Function check pump
▪
Check sensor position
056
SCREED BAKE OUT
Set flow temperature does not reach
the desired flow setpoint
temperature for 3 hours
▪
Function check mixer with mixer
motor
▪
Function check pump
▪
Check sensor position
▪
Required heat output to high
057
CHECK DATA MODUL
Module parameter is not in the
specified range
▪
Restart T-Control
▪
Check boiler parameter
058
CHECK DATA BOILER
Boiler parameter is not in the
specified range
▪
Restart T-Control
▪
Check boiler parameter
059
CAN-ID
Set up module CAN-ID not useable
-
060
INSERTION IN ACTION
when stoker temperature in
operation exceeds 70 ° C or during
ignition phase in parallel with No.61
▪
Check fuel quality
▪
Check fuel storage room (fuel
level)
▪
Clean intermediate hopper level
sensor
061
INSERTION NOT IN
ACTION
when stoker temperature in
operation exceeds 70 ° C or during
ignition phase in parallel with No.60
▪
Chimney draught to high
▪
Feeding channel leakage
▪
Check fuel quality
▪
Shortening burn out time
▪
Underrun minimum running time
062
INSERTION BACKFIRE
Stoker temperature within 30 min.
not under 70°C
▪
Chimney draught to high
▪
Boiler system leakage
▪
Check fuel quality
▪
Shortening burn out time
▪
Underrun minimum running time
▪
✆
- contracting party
Summary of Contents for firematic PELLET 120
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic PELLET 120 201 ...
Page 84: ...15 Annex 84 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 85: ...Annex 15 85 Hydraulic recommendation 2 ...
Page 86: ...15 Annex 86 15 2 Solar module Program 1 ...
Page 87: ...Annex 15 87 Program 2 ...
Page 88: ...15 Annex 88 Program 3 ...
Page 89: ...Annex 15 89 Program 4 ...
Page 90: ...15 Annex 90 Program 5 ...
Page 91: ...Annex 15 91 Program 6 ...
Page 92: ...16 Notes 92 16 NOTES ...
Page 93: ...Notes 16 93 ...