Fault reports and their corrections
10
73
No. Fault report
Cause of fault
Fault correction
081
SPEED ID-FAN
Connection failure to ID fan
▪
Check connection rotation speed
sensor
▪
Check ID-fan
▪
✆
▪
✆
- contracting party
082
GRATE CLEANING 1
Grate cleaning failure; motor
damaged; grate linkage damaged or
loosened; misaligned grate sensor
▪
Check grate cleaning motor
▪
Check grate linkage
▪
Check grate cleaning end switch
▪
✆
- contracting party
083
GRATE CLEANING 2
Failure grate cleaning; impossible to
close grate; grate got stuck; grate
linkage damaged or loosened
▪
Remove debris
▪
Check grate cleaning motor
▪
Check grate linkage
▪
Check grate cleaning end switch
▪
✆
- contracting party
084
GRATE CLEANING 3
Grate was opened during the
combustion
▪
Check grate cleaning motor
▪
Check grate linkage
▪
Check grate cleaning end switch
085
SUCTION MODE
Failure at pellet suction; fuel storage
room empty; misaligned vacutrans
flap; defect vacutrans flap sealing;
hose leakage; suction hose leaks or
is loose; suction turbine defect
▪
Adjust suction cycles
▪
Check discharge system (motor,
screw)
▪
Check fuel quality
086
SUCTION VALVE
Empty level container at compact
container
▪
Check vacutrans damper
▪
Check end switch vacutrans
damper
▪
✆
- contracting party
087
ASH CONTAINER
Ash container door is opened
▪
Connect ash container
▪
Close ash container door
090
COMB. ROOM SENSOR
Burning chamber door end switch
active; burning chamber door is
open
▪
Close burning chamber door
091
WARNING ASH
DISCHARGE
Ash discharge did not clean
respectively screw did not turn; ash
container full; debris block ash
screw; motor defect
▪
Empty ash container
▪
Remove debris
092
ERROR ASH
DISCHARGE
Ash discharge did not clean 3 times
repeatedly; ash container full; debris
block ash screw; motor defect
▪
Empty ash container
▪
Remove debris
▪
✆
- contracting party
093
ENDSW. ROOM
DISCHARGE
if digital input Room discharge
system end switch active
▪
Blockage; remove trapped fuel
▪
Check fuel quality
▪
Clean intermediate hopper level
sensor
095
CHECK ASH BOX
Set up ash container maintenance
interval exceeded
▪
Check ash container
096
BURNER STOP
if digital input Burner Stop
responding
-
097
Backup config
Fault when loading backup
▪
✆
- contracting party
104
Boiler fix difference
Boiler spread too low at nominal load
(less than 8K)
▪
Reduce pump speed (step) to get
more spread
▪
125
EXT.POWER MAX
if signal at ext.Power limit drops
below 1.3V
▪
✆
- contracting party
Summary of Contents for firematic PELLET 120
Page 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic PELLET 120 201 ...
Page 84: ...15 Annex 84 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 85: ...Annex 15 85 Hydraulic recommendation 2 ...
Page 86: ...15 Annex 86 15 2 Solar module Program 1 ...
Page 87: ...Annex 15 87 Program 2 ...
Page 88: ...15 Annex 88 Program 3 ...
Page 89: ...Annex 15 89 Program 4 ...
Page 90: ...15 Annex 90 Program 5 ...
Page 91: ...Annex 15 91 Program 6 ...
Page 92: ...16 Notes 92 16 NOTES ...
Page 93: ...Notes 16 93 ...