Temperature manager
8
21
If there is no buffer in the system, then the MUST-temperature from the individual modules is determined and
to that an adjustable temp. increase is added. The highest of these temperatures is the boiler-MUST-
temperature. To this an adjustable hysteresis is added and the result is the boiler-END-temperature (see
figure 8.4). Caution: Consider the set minimum requirement.
Figure 8.4: Example temperature manager when operation without buffer
If a time mode is applied directly on the buffer, then the required buffer-top-temperature is set directly in the
time mode module. Now it must be distinguished again if the buffer-top-temperature is higher than the
adjusted buffer-bottom-MUST-temperature. In this case the required boiler temperature is the result of the
required buffer-bottom-MUST-temperature + the adjusted temp. increase + the adjusted difference (see
figure 8.5). In this is not the case, the required boiler temperature is the result of the required tempe
the adjusted temp. increase (see Figure 8.2). Caution: Consider the set minimum requirement.
Figure 8.5: Example temperature manager when time mode with difference
Summary of Contents for pelletfire 20/20
Page 1: ...OPERATING INSTRUCTIONS Log wood pellet heating system pelletfire 20 40 ...
Page 90: ...15 Annex 90 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 91: ...Annex 15 91 Hydraulic recommendation 2 ...
Page 92: ...15 Annex 92 15 2 Solar module Program 1 ...
Page 93: ...Annex 15 93 Program 2 ...
Page 94: ...15 Annex 94 Program 3 ...
Page 95: ...Annex 15 95 Program 4 ...
Page 96: ...15 Annex 96 Program 5 ...
Page 97: ...Annex 15 97 Program 6 ...
Page 98: ...16 Notes 98 16 NOTES ...
Page 99: ...Notes 16 99 ...