Fault reports and their correction
12
Betriebsanleitung_pelletfire_Touch_Englisch_V1.2
73
Nr. Fault text
Reason
Suggestions for rectifying
053
ADDITIONAL FLUE GAS
SENSOR
Additional boiler flue gas
temperature out of range
Check sensor, replace as
necessary
Check plug, replace as necessary
Check wiring incl. Connections,
replace as necessary
054
EXTERNAL SET POINT
No Signal of external requirement or
control (if line monitoring is active)
Check sensor, replace as
necessary
Check plug, replace as necessary
Check wiring incl. Connections,
replace as necessary
055
BACK FLOW SET
Back flow set temperature could not
be reached in operation
Function check mixer with mixer
motor
Function check pump
Check sensor position
056
SCREED BAKE OUT
Error in the screed bake out
process; Flow-must temperature
could not be achieved.
Function check mixer with mixer
motor
Function check pump
Check sensor position
Required heat output to high
057
CHECK DATA MODUL
A module parameter is not in the
specified range.
Restart T-Control
Check boiler parameter
058
CHECK DATA KESSEL
A boiler parameter is not in the
specified range
Restart T-Control
Check boiler parameter
059
CAN-ID
Set up module CAN-ID not useable
-
060
INSERTION IN ACTION
Feeding screw temperature
exceeded 70°C during operation
Check fuel quality
Check fuel storage room (fuel
level)
Clean intermediate hopper level
sensor
061
INSERTION NOT IN
ACTION
Feeding screw temperature
exceeded 70°C outside of operation
Chimney draught to high
Feeding channel leakage
Check fuel quality
Shortening burn out time
Underrun minimum running time
062
INSERTION BACKFIRE
Feeding screw temperature didn´t
fall below 70°C after 30 minutes
Chimney draught to high
Boiler system leakage
Check fuel quality
Shortening burn out time
Underrun minimum running time
✆
- contracting party
063
OPEN BFP
Fault when opening the BFP
damper
Check BFP-motor
Check fuel temperature
Clean intermediate hopper level
sensor
Check drive arm
✆
- contracting party
064
CLOSE BFP
Fault when closing the BFP damper
Check BFP-motor
Check fuel temperature
Clean intermediate hopper level
sensor
Check drive arm
✆
- contracting party
Summary of Contents for pelletfire
Page 1: ...Operating instructions Log Wood Pellet heatingsystem pelletfire 20 40 ...
Page 86: ...16 Annex 86 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Hydraulic recommendation 2 ...
Page 87: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 87 16 2 Solar module Program 1 ...
Page 88: ...16 Annex 88 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 2 ...
Page 89: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 89 Program 3 ...
Page 90: ...16 Annex 90 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 4 ...
Page 91: ...Annex 16 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 91 Program 5 ...
Page 92: ...16 Annex 92 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 Program 6 ...
Page 93: ...Notes 17 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 93 17 NOTES ...
Page 94: ...17 Notes 94 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 ...
Page 95: ...Notes 17 Betriebsanleitung_pelletfire_Touch_Englisch_V1 2 95 ...