Fault reports and their Fault reports and their corrections
10
75
10.1
Not indicated faults
Fault
Cause of fault
Fault correction
Boiler output gradually
decreases
Ash/slag on the grate; fly ash
container is full; heat exchanger
heavily clogged/sooted; inferior
quality fuel
Reduce cleaning intervals or clean
manually; empty the fly ash
container; clean heat exchanger.
Desired operating temperature
is not reached
Inferior quality fuel;
previous boiler output higher than
current boiler output;
fuel level too low
Replace fuel if necessary, install
larger boiler; increase fuel level
Ash outlet at the chimney and
connection pipe
Fly ash container full; fuel contains of
excessive finds or super fines; fan
speed too high; chimney draught to
high; Ash outlet at the chimney
connection pipe
Remove fly ash; replace fuel if
necessary or retrofit flue gas
deduster; reduce speeds; retrofit
chimney draught regulator;
soot fire
In the stainless steel connecting line
seals (soot fire) must be check and
replace the seals after a fault!
Flue gas outlet on the boiler or
exhaust pipe
•
Incorrect layout / double
occupancy of the chimney
•
Leaks (defective seals on doors,
ash box, exhaust pipe ...)
•
Maintenance interval exceeded,
soot build-up, soiling, sooting in
the boiler or exhaust pipe
•
Burning chamber door opened
•
Unfavourable draft conditions, lack
of air, low delivery pressure;
•
Deflagration, unsuitable fuel
•
Design of the chimney according
to the specifications of the
assembly / installation instructions
•
Check seals and have defective /
damaged ones replaced by a
specialist.
•
Perform maintenance, clean boiler
or flue gas line.
•
Only open the combustion
chamber door in the cases
recommended according to the
instructions.
•
Check air regulation
•
Use fuel according to
specifications
Flue gas outlet on the boiler or
exhaust pipe
automatically loaded system
•
Too much fuel in the combustion
chamber
•
Check and adjust timing of the
slide
Summary of Contents for pelletstar CONDENSATION 10
Page 1: ...OPERATING INSTRUCTIONS Pellet boiler pelletstar CONDENSATION 10 60 ...
Page 86: ...15 Annex 86 Hydraulic recommendation 2 ...
Page 87: ...Annex 15 87 15 2 Solar module schematic representation Program 1 ...
Page 88: ...15 Annex 88 Program 2 ...
Page 89: ...Annex 15 89 Program 3 ...
Page 90: ...15 Annex 90 Program 4 ...
Page 91: ...Annex 15 91 Program 5 ...
Page 92: ...15 Annex 92 Program 6 ...
Page 93: ...Notes 16 93 16 NOTES ...