1500 Series or 1600 Series Electric Strike
1500 Series and 1600 Series Electric Strikes
Installation Instructions
1
Product Components
Specifications
1
2
3
ASSA ABLOY, the global leader
in door opening solutions
3
1
2
Pigtails (12 VDC and 24 VDC)
Trim Enhancer
MINIMUM WIRE GAUGE REQUIREMENTS
VOLTAGE
12VDC
24VDC
Solenoids are rated at +/- 10% indicated value.
* Applies to AC Only: 10% max duty cycle
(2 min. max on time)
200 feet or less
200 - 300 feet
300 - 400 feet
18 gauge
16 gauge
14 gauge
20 gauge
18 gauge
16 gauge
ELECTRICAL RATINGS FOR
1500E/1600E (EcoStrike™)
IN RUSH CURRENT
12 VDC
0.475A
24 VDC
0.460A
0.220A
0.215A
CONTINUOUS DUTY
10 VDC
30 VDC
VOLTAGE
NOTE:
Installation wiring for the product and wiring methods shall be in accordance with the National Electrical
Code, ANSI/NFPA 70.
NOTE:
The above table applies to Models 1500, 1500E, 1600, and 1600E.
Input voltage: 10–30 VDC, Autosensing
Ratings
Static Strength:
1,500 lbs
Dynamic Impact:
70 ft-lbs
Endurance:
250,000 cycles
Minimum Activation Duration: 1 second
0.010A
0.009A
0.005A
0.004A
ELECTRICAL RATINGS FOR
1500/1600 (Solenoid)
INTERMITTENT DUTY*
24 VDC
0.24A
12–16 VAC
0.12A
CONTINUOUS DUTY
12 VDC
24 VAC
VOLTAGE
0.24–0.32A
0.12A
-
-
-
-
UL294 Performance Levels
Destructive Attack:
Level 1 (No attack test)
Line Security:
Level I (No Line Security)
Endurance:
Level IV (100,000 cycles)
Standby Power:
Level I (No secondary power source)
4
4
5/64” Hex Wrench
5
#6-32 x 3/16” Phillips Head
Screws to Mount Trim Enhancer
5
Models 1500E and 1600E:
For Indoor Use Only
Models 1500 and 1600:
For Outdoor Use
3086006.001 Rev 3