background image

of 8

KS200

 

(Wiegand)

 

& KS210

 

(OSDP)

 

Integrated Wired Server Cabinet Lock 

Installation & Operating Instructions

Product Contents

A  KS200/KS210 Lock Body
B  Lock Interface Cable 
C  Rear Mounting Bracket
Connectors (3)
E  Screws (3) #8/32 x 1/4"  

Pan Head Phillips

F  Locking Cam

G  Screw (1) #1/4-20 x 1/2"  

Truss Head Phillips

SFIC Cam & Spacer
I  Plug-In External DPS Adapter 

(Optional)

Recommended Tools

•  Phillips #2 Screwdriver
•  Cutting Wheel (As Required)

Recommended Accessories

•  SFIC

  Mechanical Core and Keys

•  KS-DPS

  Door Open/Closed Status

•  CBL6-QC12

  6 ft Door Interface Cable

•  CBL12-QC12

  12 ft System Side Interface Cable

•  WT-2

  Securitron Wiegand Test Box

Operation

To activate the KS200/KS210 integrated electronic access control 
Server Cabinet Lock, present a known/valid credential to the card 
reader. For emergency override, insert a valid key in to the SFIC (Small 
Format Interchangeable Core) cylinder and rotate to the unlocked 
position. Upon access granted, verify functionality by lifting and 
rotating the handle to release the locking cam and open the door.

NOTE:

 The unit shall be powered by a UL294 listed power supply or access control 

output with a power limited Class 2 output. The DC input feed to the device shall be 

protected by 1A max rated over current protection provided at the installation site.
ASSA ABLOY recommends the use of Securitron and Life Safety Power power 

management products for use with ASSA ABLOY branded electromechanical 

and integrated electronic access control locking devices.

A

B

Diagram 1: 

Product Components

C

D

E

F

G

H

I

WARNING: 

This product can expose you to chemicals including lead, which is known to the state of California 

to cause cancer and birth defects or other reproductive harm. For more information go to P65Warnings.ca.gov.

KS200 

•  Contains FCC ID: 

JQ6-ICLASSBTM

•  Contains IC ID:

 

2236B-ICLASSBTM

•  WPC ID: 

ETA-SD-20210402373

KS210

•  FCC ID: 

VC3-KS210

•  IC ID:

 7160A-KS210

•  WPC ID: 

ETA-SD-20210402371

Summary of Contents for ASSA ABLOY KS200

Page 1: ...IC Small Format Interchangeable Core cylinder and rotate to the unlocked position Upon access granted verify functionality by lifting and rotating the handle to release the locking cam and open the door NOTE The unit shall be powered by a UL294 listed power supply or access control output with a power limited Class 2 output The DC input feed to the device shall be protected by 1A max rated over cu...

Page 2: ...P RS 485 SIA v2 2 IEC 60839 11 5 Card Technology HID multiCLASS SE HID Mobile Access NFC or BLE LED Visual Indicator Red Green Amber Voltage 12 to 24 VDC 10 to 15 per UL294 Environmental 32 to 122 F 10 to 50 C Weather Resistance Tested to meet IP54 Not evaluated by UL Indoor Use Only Current Consumption INPUT VOLTAGE 12 V DC 24 V DC StandbyAvg1 50mA 40mA MaxAvg2 100mA 75mA Peak3 130mA 130mA 1 Stan...

Page 3: ... QuickConnectGuide CONNECTIONS WIRING when usingElectroLynx InterfaceCables 5 OPTIONAL CONNECT the Plug In RS 485 Auxiliary Output Adapter Cable to extend control to other compatible locking devices NOTE Compatible with KS210 OSDP RS 485 models only 6 OPTIONAL CONNECT the Plug In External DPS Adapter I Diagram 6 to extend the Tamper Locked State Monitoring to include other EXTERNAL normally open s...

Page 4: ...door panel status in series with the integrated Locked State monitoring 8 ATTACH Rear Mounting Bracket C to KS200 KS210 Lock Body A using 3 Pan Head Mounting Screws E Diagram 8 9 INSTALL Locking Cam F Secure with Truss Head Screw G Diagram 9 Diagram 7 DPS Activation Diagram 8 Attach Rear Mounting Bracket C with Pan Head Screws E Diagram 9 Install Locking Cam F with Truss Head Screw G External DPS ...

Page 5: ...IC BC sold separately 1 Insert SFIC H cylinder and cam into handle Use spacer for 6 pin SFIC CAM Depth CAM Length Diagram 10 KS Cam Length Selection Diagram 11 6 or 7 pin SFIC H 10a BACK 10b SIDE 7 PIN 6 PIN PARTNO CAM CAMLENGTH CAMDEPTH Included 38mm 4 standard 1 1 2 38mm 1 25 4mm KS CAM38 38mm 1 optional 1 1 2 38mm 1 1 10 28mm KS CAM45 45mm 5 optional 1 3 4 45mm 7 10 18mm ...

Page 6: ...Green KS210 OSDP models only Cable Wire Connections EAC Integrated Wired KS200 KS210 Server Cabinet Locks ElectroLynx Wire Color Function Assignments Connections Wiring Diagram 12 Server Cabinet Wiring Example Cabinet Door 6 ft Door Interface Cable CBL6 QC12 CBL6 QC12 6 ft Door Interface Cable Lock Interface Cable CBL12 QC12 12 ft System Side Interface Cable to EAC Panel Connection 4 Pin Molex Con...

Page 7: ...stor jumper on the KS210 as shown in Diagram 7 Additional OSDP Information Available at assaabloyesh com en tech info digital asset search 1 Understanding OSDP Implementations HID Mercury FAQ 2 How OSDP Is Revolutionizing Access Control Systems Webinar 3 Why Upgrade to OSDP Infographic 4 Demystifying OSDP eBook Testing Commissioning PRIOR to applying power 1 VERIFY that the SFIC Small Format Inter...

Page 8: ... that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Model KS200 Contains FCC ID JQ6 ICLASSBTM Model KS200 Contains IC ID 2236B ICLASSBTM Canada Radio Certification This device complies with Industry Canada license exempt RSS standard s Operation is subject to the following two conditions 1 this device may not cause interference and 2 this devi...

Reviews: