Diagram 2 

Door Preparation

Diagram 3 

Insert Lock Body

3A: 

FRONT

3B:  

BACK

Mounting

1. 

LOCATE the 6" x 1" [150 x 25 mm] lock 

cutout on the door. 

Diagram 2.

2. 

INSERT the KS200/KS2100 Lock Body 

(A) into the 6" x 1" [150 x 25 mm] cutout. 

Make sure the unit bottom tabs grab 

the back of the wall. 

Diagram 3.

3. 

ENSURE KS200/KS210 Lock Body (A) 

is flush against the mounting surface 

to ensure the tamper switch on the 

back of the device is fully depressed 

and operating correctly. 

Diagram 4.

4. 

CONNECT the female, 10-position 

Hirose connector on the  Lock Interface 

Cable (B) to the back of the KS200/

KS210 Lock Body (A). 

Diagram 5.

NOTE:

 ENSURE that the  Lock Interface 

Cable (B) is not pinched or exposed prior to 

attaching the Rear Mounting Bracket (C).

•  (OPTIONAL) REMOVE the 4-Pin 

and 8-Pin Molex Connectors from 

the end of the  Lock Interface 

Cable (B) when the ElectroLynx 

Interface Cables are NOT utilized. 

•  GO TO Optional Quick Connect Guide 

(CONNECTIONS & WIRING) when 

using ElectroLynx Interface Cables.

5. 

(OPTIONAL) CONNECT the Plug-In 

RS-485 Auxiliary Output Adapter 

Cable to extend control to other 

compatible locking devices.

NOTE:

 Compatible with KS210 

OSDP RS-485 models only.

6. 

(OPTIONAL) CONNECT the Plug-In 

External DPS Adapter (I) 

Diagram 6

  

to extend the Tamper/Locked 

State Monitoring to include other 

EXTERNAL normally open switches 

that can be wired in series to monitor 

additional doors or panels.

NOTE:

 The DPS signals a secure state 

(closed) when the handle is resting 

in it the locked/latched position.
External DPS/Tamper rated for use up 

to 100 mA at 30 VDC resistive load. 

1" 

[25.4mm]

6" 

[150mm]

Diagram 4 

Tamper Switch

NOTE:

 If the tamper switch is NOT fully 

depressed, the Tamper/Locked State/DPS 

contact will report as a non-secure status. 

Tamper 

Switch

Diagram 5 

Connect  Lock Interface Cable (B)

Integrated Handle 

Locked State 

Monitoring (SPST-NO)

Plug-In External 

DPS Adaptor (3)

(Optional)

External Monitoring of 

Doors/Panels with 

Normally Open (SPST-NO) 

Switches Sold Separately

Diagram 6 

Connect (Optional) External DPS (I)

Summary of Contents for ASSA ABLOY KS200

Page 1: ...IC Small Format Interchangeable Core cylinder and rotate to the unlocked position Upon access granted verify functionality by lifting and rotating the handle to release the locking cam and open the door NOTE The unit shall be powered by a UL294 listed power supply or access control output with a power limited Class 2 output The DC input feed to the device shall be protected by 1A max rated over cu...

Page 2: ...P RS 485 SIA v2 2 IEC 60839 11 5 Card Technology HID multiCLASS SE HID Mobile Access NFC or BLE LED Visual Indicator Red Green Amber Voltage 12 to 24 VDC 10 to 15 per UL294 Environmental 32 to 122 F 10 to 50 C Weather Resistance Tested to meet IP54 Not evaluated by UL Indoor Use Only Current Consumption INPUT VOLTAGE 12 V DC 24 V DC StandbyAvg1 50mA 40mA MaxAvg2 100mA 75mA Peak3 130mA 130mA 1 Stan...

Page 3: ... QuickConnectGuide CONNECTIONS WIRING when usingElectroLynx InterfaceCables 5 OPTIONAL CONNECT the Plug In RS 485 Auxiliary Output Adapter Cable to extend control to other compatible locking devices NOTE Compatible with KS210 OSDP RS 485 models only 6 OPTIONAL CONNECT the Plug In External DPS Adapter I Diagram 6 to extend the Tamper Locked State Monitoring to include other EXTERNAL normally open s...

Page 4: ...door panel status in series with the integrated Locked State monitoring 8 ATTACH Rear Mounting Bracket C to KS200 KS210 Lock Body A using 3 Pan Head Mounting Screws E Diagram 8 9 INSTALL Locking Cam F Secure with Truss Head Screw G Diagram 9 Diagram 7 DPS Activation Diagram 8 Attach Rear Mounting Bracket C with Pan Head Screws E Diagram 9 Install Locking Cam F with Truss Head Screw G External DPS ...

Page 5: ...IC BC sold separately 1 Insert SFIC H cylinder and cam into handle Use spacer for 6 pin SFIC CAM Depth CAM Length Diagram 10 KS Cam Length Selection Diagram 11 6 or 7 pin SFIC H 10a BACK 10b SIDE 7 PIN 6 PIN PARTNO CAM CAMLENGTH CAMDEPTH Included 38mm 4 standard 1 1 2 38mm 1 25 4mm KS CAM38 38mm 1 optional 1 1 2 38mm 1 1 10 28mm KS CAM45 45mm 5 optional 1 3 4 45mm 7 10 18mm ...

Page 6: ...Green KS210 OSDP models only Cable Wire Connections EAC Integrated Wired KS200 KS210 Server Cabinet Locks ElectroLynx Wire Color Function Assignments Connections Wiring Diagram 12 Server Cabinet Wiring Example Cabinet Door 6 ft Door Interface Cable CBL6 QC12 CBL6 QC12 6 ft Door Interface Cable Lock Interface Cable CBL12 QC12 12 ft System Side Interface Cable to EAC Panel Connection 4 Pin Molex Con...

Page 7: ...stor jumper on the KS210 as shown in Diagram 7 Additional OSDP Information Available at assaabloyesh com en tech info digital asset search 1 Understanding OSDP Implementations HID Mercury FAQ 2 How OSDP Is Revolutionizing Access Control Systems Webinar 3 Why Upgrade to OSDP Infographic 4 Demystifying OSDP eBook Testing Commissioning PRIOR to applying power 1 VERIFY that the SFIC Small Format Inter...

Page 8: ... that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Model KS200 Contains FCC ID JQ6 ICLASSBTM Model KS200 Contains IC ID 2236B ICLASSBTM Canada Radio Certification This device complies with Industry Canada license exempt RSS standard s Operation is subject to the following two conditions 1 this device may not cause interference and 2 this devi...

Reviews: