Part Number 3085006.001, Rev. A
9
10.
CONNECT the 10-position Molex Micro-Fit Cable between the K200 and the EAC.
11.
ENSURE the following power cabling guidelines are followed:
Wire AWG
Supply Voltage
Allowed Cable Length (ft.)*
20 AWG
12 872
24 6679
22 AWG
12 548
24 4201
24 AWG
12 345
24 2641
* Round trip loss. V = 2 x I x R x xft
xft = V / (2 x I x R)
12.
POSITION the cable out of the way, as required.
13.
PREPARE for the single door strike plate.
a.
PEEL OFF the protective layer of the Strike Plate Template and ALIGN it to both the latch centerline and the
cabinet edge.
b.
DRILL the two pilot holes shown on the template.
c.
REMOVE the template.