Part Number 3080006.008 Rev. 3 

©2017, HES, Inc. 

                    2 

 

 

For technical support please call 1-800-626-7590 

System Overview 

     The KS100-640 wireless server cabinet lock extends access control to a server cabinet 
without the complexity and expense of running wires.  The KS100-640 cabinet lock connects 

to an access control system through the included communication hub.  The communication 

hub connects to the access control system with Wiegand wiring typical of a Wiegand reader.  
     When a credential card is presented to the reader on the lock, the request for access is 

sent wirelessly to the communication hub. The communication hub then communicates 
through Wiegand wiring to the access control system where the decision is made to grant or 

deny access.  

 

Installation Steps 

 
 
 
 
 
 
 
 
 
 
 
 
 

                                                                                              

 

 
 
 
                                                                                                          
 
 

B. Prepare the Cabinet 

C. Install the Lock 

D. Install Handing Selector 

A. Install an SFIC Core 

Summary of Contents for KS100-640 Aperio

Page 1: ...y 2 4 GHz IEEE 802 15 4 using AES 128bit encryption Hub Power Requirement 8 24VDC 250mA Lock Power 48VDC Power over Ethernet PoE 802 3af compliant OR 24VDC Power Supply Supply not provided Power Consumption Less than 1W Operating Temperature 10C to 50C Holding Force 250 lbs FCC Part 15 Compliant Industry Canada Compliant BHMA A156 3 A156 36 A156 25 Compliant Credentials Supported 125kHz Proximity ...

Page 2: ... the included communication hub The communication hub connects to the access control system with Wiegand wiring typical of a Wiegand reader When a credential card is presented to the reader on the lock the request for access is sent wirelessly to the communication hub The communication hub then communicates through Wiegand wiring to the access control system where the decision is made to grant or ...

Page 3: ... Medeco and Sargent 6 or 7 pin SFIC cores 2 Prepare the Rack Locate the 25mm x 150mm lock cutout on the door some doors may require modification 1 Verify 48V POE power is available at the rack 2 Re use the existing cam if possible 3 One cam is supplied CAM CAM LENGTH CAM DEPTH CAM 1 38mm 1 1 2 16mm 5 8 2 Insert SFIC into lock 7 pin 1 Insert Cam into SFIC Use the included Spacer with 6 pin SFICs 6 ...

Page 4: ...ded Optional Switch 1 SPST NO Provided Extending the DPS Circuit A Remove the DPS jumper B Connect the included DPS extension cable C Connect additional normally open DPS switches as shown to monitor additional panels 2 Select Power source A 24VDC Supply OR B 48V PoE Connect 24VDC cable to lock Connect 24VDC power supply not provided to 24VDC cable Red wire 24VDC black wire Ground 24VDC cable A B ...

Page 5: ...stalling the Handing Selector Note Be careful not to insert snap the handle all the way in as the lever will lock 2 Position the arrows to point toward the door edge as shown above 1 Insert handing selector into lock Door edge 3 Secure cam with screw ...

Page 6: ...Part Number 3080006 008 Rev 3 2017 HES Inc 6 This page intentionally left blank ...

Page 7: ...Part Number 3080006 008 Rev 3 2017 HES Inc 7 This page intentionally left blank ...

Page 8: ...ference that may cause undesired operation Conformité aux normes FCC Cet équipement a été testé et trouvé conforme aux limites pour un dispositif numérique de classe B conformément à la Partie 15 des règlements de la FCC Ces limites sont conçues pour fournir une protection raisonnable contre les interférences nuisibles dans une installation résidentielle Cet équipement génère utilise et peut émett...