Parameter settings 

5.1  Control parameters  

This option makes it possible to change the value of parameters available in the selected installation scheme. In order to change parameters: 
Press the following key combination: starting point - MAIN SCREEN: entry into the 

MENU

 

, get to the option named 

Parameters settings

 

, enter the 

Parameter settings

 

menu 

, get to the 

Control parameters

 option 

, choose appropriate parameters 

 or 

, edit 

, change values 

 or 

, accept values 

 (a continuous sound 

signal), return to the main screen 

 

 

.

 

 

ATTENTION ! Description of all the available parameters can be found in Table 3 – pages16-17 

The display shows current option level and the controller values with the use of the ▼and ▲ cursors. The down cursor ▼ shows that there are parameters available 

below the currently displayed options, whereas the up cursor ▲, indicates that there are parameters available above the currently displayed ones. The combination of 

buttons for selected scheme no 3 is presented below. 

5.2  Time program C 

This option allows for setting a time program in which a device denoted by C (circulation pump, pool pump) in a given installation scheme will be working. In order to set or change the 
C time program of devices: 

Press the following key combination: starting point - MAIN SCREEN: enter the 

MENU 

with

 

 (enter password), get to the option named 

Parameters settings 

with 

, enter the 

Parameter settings

 menu with 

, get to the option named 

Time program C

 with 

, enter the option named 

Time program C

 with 

, select time with 

 or 

, accept 

operation time (white square) or cancel operation time with 

, accept and return (a continuous sound) with 

, return to the main screen with 

 

 

ATTENTION ! Time intervals are divided into 24h operation periods, settings for each hour are selected separately by marking it with a white square. The number of 

squares marks the number of operation hours. Week days have been divided into three groups: Monday - Friday (Mo-Fr), Saturday (Sat), Sunday (Sun). 

5.3  Circulation parameters 

This option allows for setting all parameters connected with the operation of the tap water circulation pump. To change parameters of the C pump: 

Press the following key combination: starting point – MAIN SCREEN: enter the 

MENU

 with 

 (enter password), get to the option named 

Parameters settings

 with 

, enter the 

Parameters settings

 menu 

, get to the option named 

Circulation param. 

, select the parameter to be changed with 

 or 

, edit the parameter 

, change its value 

with 

 or 

, accept (a continuous sound) 

, return to the main screen with

 

 

ATTENTION! For description of all available parameters for the circulation pump, see Table 3 – pages 16-17

 

5.4  Time program K 

This option allows for setting a time program in which a device denoted by K (boiler, electrical heat, heat pump) in a given diagram will be working. In order to set or change the K time 
program of devices: 

Press the following key combination: starting point - MAIN SCREEN: enter the 

MENU

 with 

 (enter password), get to the option named 

Parameters setting

 with

, enter the 

Parameter settings

 menu with 

, get to the option named 

Time program K

 with 

 

 

, enter the option named 

Time program K

 with

, select time with 

 or 

accept operation time (white square) or cancel operation time with 

, accept and return (a continuous sound) with 

, return to the main screen with 

 

.

 

ATTENTION! Hourly setting of K are identical to those of the Time program C.  

5.5  Heat transfer fluid 

A  parameter connected  with  liquid  specific  heat,  it  corresponds  to  a  given solidification  temperature  of  a  heat  carrier.  In  order  to  define  this  parameter  read  liquid  solidification 
temperature from the package or contact the seller. In order to set or change the solidification temperature of the liquid used: 

Press the following key combination: starting point - MAIN SCREEN: entry into the 

MENU

 with

 (enter password), get to the option named 

Parameters setting

 with 

, enter the 

Parameter settings

 menu with 

, get to the option named 

Heat carrier

 with 

 

 

 

, enter the option named 

Heat carrier

 with

, change values with 

 or 

accept and return (a continuous sound) with 

, return to the main screen with 

 

.

 

ATTENTION ! This parameter is needed for correct calculation of solar collector instantaneous power and summing thermal energy.  

5.6  Flow rate 

A parameter connected with heat carrier flow. In order to make correct settings: 

Press the following key combination: starting point - MAIN SCREEN: enter the 

MENU 

with 

 (enter password), get to the option named 

Parameters setting

 with 

, enter the 

Parameter settings

 menu with 

, get to the option named 

Flow rate 

with 

 

 

 

 

, enter the option named 

Flow rate 

with 

, select the parameter to be changed 

with 

 or 

, edit with 

, change values with 

 or 

, accept (a continuous sound) with 

, return to the main screen with 

 

 

ATTENTION ! Correct flow rate depends on the sort of collectors, type of collectors and overall dimensions. 

Set the recommended minimum flow rate to 0.3 l/min for 1 m

2

 of active area of the collector (example: 2 collectors with active area of 2.0 m

2

 each – minimum flow rate is: 2 

 2 = 4 

 

0.3 = 1.2 l/min. 
Set the nominal (maximum) flow rate to 1 l/min for 1 m

2

 of active area of the collector (example: 2 collectors with active area of 2.0 m

2

 each – nominal flow rate is: 2 

 2 = 4 

 1.0 = 

4.0 l/min. 

The controller enables cooperation with a mechanical rotameter or

 an

 electronic flow meter of the G-916 type or any other electronic flow meter.   

Select the main flow meter connected to 

FLOW1

 terminals.

 

The second flow meter connected to 

FLOW2

 terminals is by default set as 

Electronic G-916.

 

Measurement: Electr.G916 

– cooperation

 with an electronic G-916 flow meter. 

The controller reads the number of impulses and converts it into the real flow (liters per minute). 

 

 

Nominal 

 

flow rate

 – entry to the nominal flow rate option results in switching P collector pumps on with maximum efficiency. Enter the calculated flow rate value that 

results from the number of collectors in the system into the edition field. Next, set the required flow in such a way that the “

Current” 

value corresponds to the calculated 

value entered before. The required flow can be obtained by changing the rotational speed in option 

Collector Pump.

 

 

Summary of Contents for GH26-P09

Page 1: ...USER MANUAL OF AN INDEPENDENT REGULATION BLOCK GH26 P09 GH26 P09A Controller of a solar collector system applicable from version 0 1a ...

Page 2: ...t Maximum current intensity 2A O2 Transmitter output no voltage output relay Maximum current intensity 2A S1 S2 NC normally closed S2 S3 NO normally open May operate as voltage output applying voltage to S2 will result in changeover voltage output O3 230V output relay Maximum current intensity 2A O4 230V output bridging inside the controller It is allowed to bridge outside with a terminal of a rel...

Page 3: ...ch on for the blanking period set Screen blanking aims at limiting energy consumption Connect the electrical plug to the socket equipped with a protective terminal and protected with RCD It is forbidden to install pump units in close vicinity of open flames high temperatures and storage of flammable materials 3 2 Controller keyboard description The controller has a touch keyboard with 7 keys which...

Page 4: ...erence pump ON value than the T2 temperature in the lower part of the heater If the heater s temperature reaches the set value of MaxTemp T2 OFF collector s pump the P pump will be switched off Additionally in order to avoid unstable pump operation when the temperature on the sensor changes switch on and switch off hysteresis has been used Controlling the P collector pump Regulation of collector s...

Page 5: ...to boiler switch on and switch off temperatures An example of a table of resistances depending on the manufacturer of a given boiler has been presented in the table below ATTENTION The original tap water temperature sensor remains disconnected and replaced by 2 wire cable from the controller GH26 Table 2 Resistor resistance for selected boiler manufacturers Fig 5 Schematic and electrical diagram o...

Page 6: ...larly as in scheme no 1 description in point 4 1 Controlling the C circulation pump Similarly as in scheme no 2 description in point 4 2 Controlling K boiler pump The K boiler pump will be switched on if the T5 temperature at the boiler outlet gets higher by the Temperature difference ON add pump valve value than the T4 temperature in the upper part of the heater The pump will remain switched on u...

Page 7: ...he set allowable value of Max temp T4 OFF heat source Fig 9 Schematic and electrical diagram of installation no 7 4 8 Double heater system makes it possible to provide additional solar energy heating for the boiler heater with the use of a circulation return scheme no 8 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the C circulation pump Similarl...

Page 8: ...be found in the Parameter settings menu The C pool pump is always switched on when pool water is heated with solar collectors ATTENTION If the C pool pump is switched offwhen the solar collector pump is working and the U valve is set to the pool may damage the piping system of the pool circuit In order to protect the exchanger against lack of heat collection by the pool pump a T4 sensor should be ...

Page 9: ... scheme Controlling the C circulation pump Similarly as in scheme no 2 description in point 4 2 Fig 14 Schematic and electrical diagram of installation no 12 4 13 The system with a buffer tank used for cooperation with a central heating installation scheme no 13 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the C boiler pump The C boiler pump is ...

Page 10: ...ers have been used in the diagram Max temp T4 OFF heat source for heating with the use of an electrical boiler or a liquid fuel boiler and Max water temperature from boiler C for heating with the use of a fireplace or a solid fuel boiler for heating water in the upper part of the combi heater measured by the T4 sensor Fig 16 Schematic and electrical diagram of installation no 14 4 15 Tap water hea...

Page 11: ...ure in the A heater reaches Max temp T4 OFF heat source When the T4 temperature exceeds the set value the controller switches the valve back into the B heater direction and switches the P collector pump off When water is being heated in the A heater once an hour for 5 minutes the controller forces P collector pump switch off in order to check the conditions for heating the B heater and switch heat...

Page 12: ... Fig 20 Schematic and electrical diagram of installation no 18 4 19 Tap water heating system controlling solar collector pump mixing pump and system of solar energy heating for the boiler heater with the use of a circulation return scheme no 19 Controlling the P collector pump Similarly as in scheme no 1 description in point 4 1 Controlling the K mixing pump Similarly as in scheme no 7 description...

Page 13: ...option named Parameters setting with enter the Parameter settings menu with get to the option named Time program K with enter the option named Time program K with select time with or accept operation time white square or cancel operation time with accept and return a continuous sound with return to the main screen with ATTENTION Hourly setting of K are identical to those of the Time program C 5 5 ...

Page 14: ...er the flow value that results from the number of collectors in the system into the edition field Next set the required flow rate value in such a way that the Current value corresponds to the calculated value entered before The required flow can be obtained by changing the rotational speed in option Collector pump ATTENTION Leaving the field unchanged or entering wrong value does not affect the op...

Page 15: ... water heater by switching the solar collector pumps on in a specific time interval starting from 0 00 to the time set in the Stop cooling at h parameter The cooling option will be active if cooling is on Night cooling Yes and the T2 temperature in the heater is higher or equal to the set Start cooling temperature Cooling will remain active until the heater gets cooler to the Stop cooling temperat...

Page 16: ...ption of its functions has been included in point 4 for selected external devices only 10 85 C 50 C Max water temperature from boiler C A parameter only used in schemes no 14 and 18 It defines the maximum temperature of water measured by the T4 sensor for the operation of C pump cooperating with the water circuit of fireplace or solid fuel boiler 10 85 C 60 C Regulation of collector s pump P solar...

Page 17: ...the circulating pump Time of switching off the C circulation pump in a set cyclic mode according to the preset working times 1 59min 10min Table 3 Controller parameter description 13 Error alarms and controller notifications Temperature sensor error check sensors for visual condition or for proper connection to the controller The controller checks whether temperature sensors have been connected If...

Page 18: ...ing with the operation of the system and the controller Lack of required heater protection by titanium anode applies to the GH26 P09A controller only The controller is used as a power supply for the titanium anode placed in the water heater for protection of the latter against corrosion The lack of anode incorrect connection or damage to the anode circuit will switch on the sound alarm and display...