3
2.4.2 Enter Configuration Mode
Method 1:
After wiring, power on and press button “Deploy” longer than 5S to make LoRa device enter
the configuration mode. After that, the LINK/ACT indicator lights flash at a fixed frequency
(flashing once per second) and release the button.
Method 2:
Press the button “Deploy” to power up the module, it will enter the configuration mode
directly. And then release the button. The Link/ACT indicator light will flash at a fixed
frequency (flashing once per second).
2.4.3 Open the Software
Open the software of LoRaWAN series products. Select the corresponding COM port in the
“Communication Connection” part, and then click “Open the Port”, like the following picture.
2.4.4 Parameters Configuration
There are six parts in the parameters configuration: internet access, serial port parameters
configuration, devices definition, register definition, upload/download data definition. Now
we need to configure the parameters of internet access & serial port.
(1)Internet Access: the unique code of LoraWAN device and Appkey cannot be modified.
(2)Serial Port Parameters Configuration: Close RS485-1 and RS485-2
Parameter Configuration Process:
After opening the serial ports, click “Read”. Then it will indicate “Completed”. If it indicates
“Time Out”, please check whether the LoRa device enters the configuration mode.
After completing operation, the host computer will read out the current configured
parameters.
If you need to modify corresponding parameters, click “Write” then it will indicate
“Completed”.
Click “Read” again to check whether configuration is correct. Click “Restart” to exit
configuration mode.