background image

52

Safety Inspection

1.

Check all thermostats and high limit settings.

2.

During the following safety checks leave manome-
ters hooked up, check and record.

3.

If other gas-fired appliances in the room are on the
same gas main, check all pressures on the Hi
Delta with all other equipment running.

4.

Check thermostats for ON-OFF operation.

5.

Check high limits for ON-OFF operation.

6.

While in operation, check flow switch operation.

7.

Check the low gas pressure switch. (For proper
adjustment, use the attached manometers, if
available, to set pressure. The scales on the
switch are approximate only.) Low gas pressure
switch must be set at 5.0 in. WC for natural gas
and 10.0 in. WC for propane gas.

8.

Make sure that the high gas pressure switch (op-
tional) is set to 1.0 in. WC above manifold pres-
sure.

Follow-Up

Safety checks must be recorded as performed.

Turn heater on. After main burner ignition:

1.

Check manometer for proper reading.

2.

Cycle heater several times and re-check readings.

3.

Remove all manometers and replace caps and
screws. 

4.

Replace all gas pressure caps.

5.

Check for gas leaks one more time.

Pilot Turn-Down Test

The Hi Delta heaters, depending on their size, have
one to three burner sections. Each burner section is
supplied gas by gas valves incorporated into a single
valve body. A maximum of three burner sections may
be controlled by a single hot surface ignition system.
The middle of the three burner sections is ignited
directly with a hot surface ignition system.

The burner section that is ignited directly by the hot
surface ignition system serves as a supervised pilot to
light the burner sections on either side of it. The burn-
er sections on either side of the supervised section
(pilot) are electrically interlocked with the supervised
ignition system so as they are not energized unless
flame is proven on the center section which is acting
as a pilot to light the right and left-hand sections.

The pilot turn-down test is conducted as follows:

1.

Turn off manual valves on non-supervised burner
sections.

2.

Turn on electrical power and adjust thermostat to
call for heat.

3.

Wait for completion of ignition sequence to light
burner section being utilized as a pilot for those
turned off in step 1 above.

4.

Gradually reduce manifold pressure (flame) on
supervised burner section by slowly closing man-
ual gas valve. Watch for shut-down due to loss of
supervised flame signal as pressure is being re-
duced. Flame signal should be lost before mani-
fold pressure goes below 2.0 in. WC for natural
gas and 6.0 in. WC for propane gas.

Leak Test Procedure: Dual-Seat Gas
Valves

Proper leak testing requires three pressure test points
in the gas train.

Test point A is upstream of the automatic gas valve. On
the first automatic valve, this is a bleedle valve. On the
other valves, this is a plugged port. The bleedle valve
on the first valve may be used for all the other valves
as well.

Test point B is a bleedle valve located between the two
automatic gas valve seats.

Test point C is located downstream of both automatic
gas valve seats and upstream of the manual valve. On
the manual valve, this is a bleedle valve. Identical
readings will be found at the plugged port labeled as
Alternate C.

Refer to Fig. 44. The numbers on the diagram refer to
the steps below:

These tests are to be conducted with the electrical
power to the heater turned off.

Summary of Contents for 1262A

Page 1: ...e To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call yo...

Page 2: ...2...

Page 3: ...rical Power Connections 22 Field Wiring Connection 23 Venting 25 Changing the Flue Outlet 27 Venting Installation Tips 28 Venting Configurations 28 Controls 33 Outdoor Installation 33 Heater Sequence...

Page 4: ...f the control system and any gas control which has been under water WARNING To minimize the possibility of improper operation serious personal injury fire or damage to the heater Always keep the area...

Page 5: ...laced in kind only per Raypak s standard war ranties Model Identification The model identification number and heater serial number are found on the heater rating plate located on the lower right outsi...

Page 6: ...6 Component Locations Fig 1 Component Locations Back Fig 2 Component Locations Left Side Panels removed for clarity Fig 3 Component Locations Front...

Page 7: ...m Burners per Valve Stages Fire at Stage Model No 1 1A 2 3 4 1 2 3 4 1 2 3 4 992A 6 3 2 1 1 2 1 2 3 54 82 100 1262A 5 3 3 3 1 1 2 1 2 3 1 2 3 4 36 57 79 100 1532A 6 4 4 3 1 1 2 1 2 3 1 2 3 4 35 59 82...

Page 8: ...stream and read the thermometer NOTE When this water heater is supplying general purpose hot water for use by individuals a thermo statically controlled mixing valve for reducing point of use water t...

Page 9: ...d turn the wheel to the desired setting See Fig 4 CAUTION Hotter water increases the risk of scald ing There is a hot water scald potential if the thermo stat is set too high Fig 4 Temperature Control...

Page 10: ...e 4 ft 1 2m below or to side of opening 1 ft 30 cm above opening 3 ft 91 cm K Clearance to mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3m horizontally 6 ft 1 83m L Clearance above pav...

Page 11: ...d location without movement or removal of the heater Service clearances less than the minimums may require removal of the heater to service either the heat exchanger or the burner tray In either case...

Page 12: ...point communicat ing with the outdoors The total cross sectional area shall be at least 1 in 2 of free area per 20 000 BTUH 111 mm2 per kW of total input rating of all equipment in the room when the...

Page 13: ...han 100 in 2 645 cm2 One opening shall commence within 12 in 305 mm of the top and one opening shall commence within 12 in 305 mm of the bottom of the enclosure The mini mum dimension of air openings...

Page 14: ...ion air must be drawn from the air outside of the building the mechanical equip ment room must communicate directly with the out doors of not less than 1 in 2 for each 30 000 BTUH mm2 per kW of total...

Page 15: ...nections to the heater and the rest of the system prior to operation This is particularly true for hydronic systems using expensive glycol based anti freeze Raypak recommends conducting the hydrostati...

Page 16: ...alve system such as a three way proportional valve or a modulating two way valve to control the bypass should be utilized Cold Water Run Cold water run differs from cold water start in that the system...

Page 17: ...l valves or other automatic means to prevent gravity circulation of the heater water during the cooling cycle It is highly recommend ed that the piping be insulated Air Separation Expansion Tank All h...

Page 18: ...32 16 5 2 24 4 1802A 30 101 10 7 2 15 5 23 132 18 3 2 26 1 23 132 18 3 2 26 1 2002A 30 112 13 9 2 19 7 26 132 19 0 2 26 9 26 132 19 0 2 26 9 2072A 30 116 14 8 2 21 0 27 132 19 0 2 26 9 27 132 19 0 2 2...

Page 19: ...emperature is 105 F NOTE Opening the valve will increase the temperature and closing the valve will decrease the temperature 5 If this process does not raise the inlet water tem Fig 14 Single Pool Hea...

Page 20: ...severe dam age to your heater and associated equipment Total Dissolved Solids Total dissolved solids TDS is the measure of all min erals and solids that are dissolved in the water The concentration o...

Page 21: ...protected from physical damage and freezing where required Reversing Gas Supply Connection Reversing the standard fuel connection from the left hand to the right hand side is a simple field operation...

Page 22: ...ssure Fig 17 Gas Valve Electrical Power Connections Installations must follow these codes National Electrical Code and any other national state provincial or local codes or regulations hav ing jurisdi...

Page 23: ...working with any electrical connections or components 3 Observe proper wire colors while making electri cal connections Many electronic controls are po larity sensitive Components damaged by improp e...

Page 24: ...ctrical power to the heater is discon nected to avoid potential serious injury or damage to components Fig 21 On Off Wiring Connections Fig 22 2 Stage Wiring Connections Fig 23 3 Stage Wiring Connecti...

Page 25: ...and CSA C22 1 C E C Part 1 in Canada 2 STAGE TANKSTAT STAGE 1 CONNECTION STAGE 2 CONNECTION OR STAGE 1 CONNECTION OF HEATER 2 ATTACH STAGE 1 CONNECTIONS ON HEATER TO STAGE 1 CONNECTION ON TANKSTAT ATT...

Page 26: ...struct a window view if the ter mination is installed near windows 4 Prevailing winds in combination with below freez ing temperatures can cause freezing of conden sate and water ice build up on build...

Page 27: ...ct vent installations require a 4 ft clearance between the ends of vent caps located on the same horizontal plane Canadian Installations Refer to latest edition of B149 1 A vent shall not terminate 1...

Page 28: ...y CAUTION The silicone vent gaskets must be prop erly reinstalled to prevent flue gas leakage Replace any torn or worn vent gaskets WARNING Examine the venting system at least once a year Check all jo...

Page 29: ...1 Seal any unused opening in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and verify there is no block age restriction leakage corrosion or othe...

Page 30: ...ed 70 equivalent ft in length If horizontal run exceeds 70 equivalent ft an appropri ately sized extractor must be used Each elbow used is equal to 10 ft of straight pipe This will allow installa tion...

Page 31: ...rtical height exceeds 25 ft consult factory prior to installation Fig 29 Direct Vent Horizontal Through the Wall The total length of the through the wall flue cannot exceed 40 equivalent ft in length...

Page 32: ...as vent pipes listed for use with Category III gas burning heaters such as the AL29 4C stainless steel vents offered by Heat Fab Inc 800 772 0739 Protech System Inc 800 766 3473 or Z Flex 800 654 5600...

Page 33: ...not locate adjacent to any window door walk way or gravity air intake The vent must be lo cated a minimum of 4 ft horizontally from such ar eas 4 Install above grade level and above normal snow level...

Page 34: ...c board are low water cut off optional blocked vent switch manual vent temp switch optional manu al reset high limit low gas pressure switch option al high gas pressure switch optional and auto reset...

Page 35: ...safety valve PVC Vent Limit Red Vent temperature exceeds limits Auto Reset High Limit Red Auto reset option Table M LED Indicators 25 The flow light is energized located on the diag nostics panel 26...

Page 36: ...e times prior to ignition lockout 42 After gas valve 1 opens and flame rectification is received time delay relay 1 TD 1 starts a 5 sec ond countdown 43 After the 5 second countdown from TD 1 24 VAC i...

Page 37: ...ion module 1 closes contacts allowing the 24VAC from K 3 to go to ground and the K 3 contacts close to allow the unit to fire at stage 3 20 After the standby switch is placed into the ON position a 24...

Page 38: ...onnection on the CPW board 46 The temperature controller closes the stage 2 con tacts and gas valve 2 in energized 47 The stage 2 LED on the diagnostics display board is now illuminated 48 The tempera...

Page 39: ...nt is now powered If the switch is ON and there is no call for heat CFH the heater is in standby mode 19 Power is applied to the coil of K 3 If an ignition lockout occurs ignition module 1 closes cont...

Page 40: ...4 After gas valve 1 opens and flame rectification is received time delay relay 1 TD1 starts a 5 sec ond countdown 45 After the 5 second countdown from TD 1 time delay relay 2 receives 24 VAC 46 Gas va...

Page 41: ...gnition lockout 4 Flashes Low igniter current 5 Flashes Low 24 VAC check control supply voltage 6 Flashes Internal fault Replace module Fig 32 Ignition Module Table N Ignition Module Diagnostic LED Co...

Page 42: ...alve to ensure that suffi cient gas pressure is present for proper regulator per formance The low gas pressure switch automatically shuts down the heater if gas supply drops below the factory setting...

Page 43: ...i Delta CAUTION Proper installation of flue venting is criti cal for the safe and efficient operation of the boiler NOTE For additional information on appliance cat egorization see appropriate code NF...

Page 44: ...of regulators relief valves or other equipment 8 Locate and guard vent termination to prevent acci dental contact by people or pets 9 DO NOT terminate vent in window well stairwell alcove courtyard or...

Page 45: ...ir Galvanized Steel PVC ABS CPVC 40 75 Subtract 10 ft per elbow Max 3 elbows Maximum combustion air duct length terminated at 100 equivalent ft pressure reading must be between 0 01 and 0 1 in WC as m...

Page 46: ...onsidered in the overall length of the venting system Care must be taken during assembly that all joints are sealed properly and are airtight The vent must be installed to prevent the potential ac cum...

Page 47: ...Steel PVC ABS CPVC 40 75 Vent lengths are based on a lateral length of 2 ft Refer to the latest edition of the NFGC for further details When vertical height exceeds 25 ft consult factory prior to inst...

Page 48: ...48 Wiring Diagrams...

Page 49: ...49...

Page 50: ...uilding Immediately call your gas supplier from a neigh bor s telephone Follow the gas supplier s instruc tions WARNING If you do not follow these instructions exactly a fire or explosion may result c...

Page 51: ...ilure Failure to do this may burn out 120V 24V trans former or may cause other safety control damage or failure Start Up Blower Adjustment 1 Turn off power 2 Unplug cap at pressure switches and connec...

Page 52: ...sed pilot to light the burner sections on either side of it The burn er sections on either side of the supervised section pilot are electrically interlocked with the supervised ignition system so as t...

Page 53: ...restore electrical power to heater Fig 44 Leak Test This completes leak testing for a single Hi Delta mani fold riser Repeat steps 1 8 for each riser Post Start Up Check Check off steps as completed 1...

Page 54: ...rn on main manual gas valve 7 Wait 5 minutes to clear out any gas Then smell for gas especially near the floor If you then smell gas STOP Follow the steps in the safety informa tion on the front cover...

Page 55: ...1 800 927 2975 Outside California 1 800 627 2975 Inside California Replace gas valve Are the gas valve settings correct Replace fan relay Replace fan Replace air pressure switch Correct the air settin...

Page 56: ...e vapors and liq uids 4 Check for and remove any obstruction to the flow of combustion or ventilation air to heater 5 Follow pre start up check in the Start up section 6 Visually inspect burner flame...

Page 57: ...4 Check piping and wiring of all interlocks and shut off valves 5 Inspect burners Annually 1 Test flame failure detection system and pilot turn down See Pilot Turn Down Test Procedure page 52 2 Test...

Page 58: ...ontaminated ar eas this may also experience deterioration Products causing contaminated combustion air spray cans containing chloro fluorocarbons permanent wave solutions chlorinated waxes cleaners ch...

Page 59: ...o water PARTS REPLACEMENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returned to Raypak if requested with transportation charges prepaid an...

Page 60: ...al Dissolved Solids TDS must be no greater than 2500 PPM PARTS REPLACEMENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returned to Raypak if...

Page 61: ...61...

Page 62: ...62...

Page 63: ...63...

Page 64: ...raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Raypak Canada Limited 2805 Slough St Mississauga Ontario Canada L4T 1G2 905 677 7999 Fax 905 677 8036 Litho in U...

Reviews: