iCLASS SE
INSTALLATION GUIDE
4
PLT-01051, A.
6
R90
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved.
P2
P1
7
1 7
1
HOLD
RED
DRAIN +VDC
GND GRN BEEP
GPIO1 GPIO2
OC/TMPR
DA
TA1/CLK
DA
TA0/DA
TA
GPIO3 GPIO4
7
1 7
1
P1
P2
HOLD
RED
DRAIN +VDC
GND GRN BEEP GPIO1 GPIO2
OC/TMPR
DA
TA1/CLK
DA
TA0/DA
TA
GPIO3 GPIO4
ATTENTION
Observe precautions for handling
ELECTROSTATIC SENSITIVE DEVICES
Wiring
C
ableado
C
âblage
f
iação
V
erdrahtung
C
ablaggio
配線
布线
배선
П
ОдКЛючЕнИЕ
ПрОвОдОв
2
Terminal Description
Terminal
Description
P1-1
Beeper Input
P2-1
GPIO4 (RS485-Y / TXA)
P1-2
LED Input (GRN)
P2-2
GPIO3 (RS485-Z / TXB)
P1-3
Ground (RTN)
P2-3
** Wiegand Data 0 / Data
P1-4
+VDC
P2-4
** Wiegand Data 1 / Clock
P1-5
Unused
P2-5
* Open Collector Output / Tamper
P1-6
LED Input (RED)
P2-6
GPIO2/OSDP (RS485-RXB)
P1-7
Hold Input
P2-7
GPIO1/OSDP (RS485-RXA)
Note:
Terminal IDs have changed from the previous generation of R90 Readers. When replacing an existing R90A reader, the connector wiring must be modified to that shown in the table prior to installing the
R90E reader.
*
Tamper Output - When activated, output synchronizes to ground (default).
**
Dependent upon reader configuration. See the HTOG for Wiegand and Clock-in-Data configurations.
Note:
Previous iCLASS readers had reversed RS-485 wiring (P2-7 & P2-6 - A & B). When upgrading to an iCLASS SE reader, ensure proper connections as defined below.
Note:
It’s possible to reuse existing Wiegand wiring for OSDP, however, using simple stranded cable typical of Wiegand access control readers is usually not meeting the RS485 twisted pair
recommendations.
Note:
For OSDP cable lengths greater than 200ft. (61M) or EMF interference, install 120Ω +/- 2Ω resistor across RS-485 termination ends.
Note:
Wiring the reader incorrectly may permanently damage the reader.
Note:
With a keypad reader, operating as 26 bit emulation; upon power up you have 5 seconds to enter the facility code followed by #. If unsuccessful, the reader LED displays solid Red. Power-cycle the
reader and retry entering the facility code. The facility code needs to be manually entered as 3 digits (i.e. if facility code is 10 enter 0-1-0-#).
Note:
SE readers only use facility codes between 1-255,
and there is no default facility code. Once the facility code has been entered, the LED will display Violet and then to a final Red. Then power-cycle the reader.
Note:
When using a keypad, if there
are 2 short beeps after entering your PIN, the reader does not have a facility code configured yet. In this event, an Admin will need to be power-cycle the reader and enter the facility code before the
reader will accept your PIN.