background image

USER'S GUIDE R18 AXIAL FAN , Iss: 6.05.2021

Recommended cable for power supply is a heat resistant PVC or other cable of appropriate quality (105°C) acc. to IEC 60227-5, e.g. H05V2V2-F, 4G
1.5 mm² (min.1.0 mm² - max. 2.5 mm² for stranded leads or max. 2.5mm² for solid conductors), outer diameter 6.0 - 11mm. Power supply cable could
include also additional leads for alarm circuit, e.g. H05V2V2-F, 6G 1 mm². 
Recommended cable for alarm circuit is an ordinary PVC cable acc. to IEC 60227-5, e.g. H05V2V2-F, 2X 1 mm² (min.2X 0.50mm² - max. 2X 1.5mm²),
outer diameter 5.0 - 9.5mm.
Recommended cable for control circuit is an ordinary PVC cable, e.g. H05VV-F, 5X 0,5 mm² (min. 0,25 mm² - max. 0,75 mm² ) , no longer than 2m,
outer diameter 6.0 - 11mm and must be sufficient separated and isolated from the supply circuit and alarm circuit leads. No cable crossing inside the
connection box is allowed.
The connection cables must be prepared before opening the terminal cover. Only open the terminal cover in dry conditions and make sure that the
remains of conductors do not fall into the terminal compartment.
Follow the instructions for preparing the connecting cables as shown in the figure below. Cable sheath needs to stripped in the length of 50 - 60mm.
Ends of stranded wires needs to be provided with insulated ferrule (pin) length 8-10mm.
The fan is equipped with push-in spring terminals type PHOENIX SPTA or eqvivalent, that allow very easy connection.
A screwdriver of 0.6X3.5mm is necessary tool to remove conductor from the mains terminals and a screwdriver of 2.5x0.5mm is necessary tool to
remove conductor from the control circuit terminals.
Fan performed with terminal box is as supplied fitted with a sealing plug in the cable glands as a preventive against ingress of water or moisture inside
the terminal box. If the cable is not installed through the cable gland, sealing plug must remain in the gland! Connection box screws have to be
tightened with torque of 2,0Nm - 2,5Nm.  

Secure connection cable to the fan guard grill or to the motor holder with cable fasteners so that the water flows away from the cable and cable gland.
Try to maintain as much distance between supply and control cable as possible (recommended distance > 5cm). 

Cable-end of the fan must be connected in a dry environment to prevent that water penetrate through cable into motor housing.

Where the fan is installed in shaft-horizontal position, the cable exit on the motor must be in down position.

Before putting into operation, check the resistance of protective-earth circuit of the entire application. Cross-sectional area and material of PE conductor
may be the same as cross-sectional of phase conductor or see guide regarding PE conductor : standard EN 61800-5-1. 

A second protective earthing conductor must be installed to ensure requirements of standard "

EN 61800-5-1 , 4.3.5.5.2 Touch current in case of failure

of protective earthing conductor

". For that purpose an additional M4 of 12mm depth hole or additional PE terminal is provided on motor housing and

marked with PE symbol. More information about dimensions of second PE conductor please find in guidelines of mentioned EN or equivalent standard

(a cross-section of second Cu conductor should never be less than 2.5mm

2

).

CONNECTING DIAGRAM : See appended technical drawing - CONNECTING DIAGRAM   0302-0-0023

POWER SUPPLY : L1, L2, L3, PE

CONTROL CIRCUIT:

Control circuit is SELV isolated from main power supply (including an external power supply for sensors).

Enable: I01 - +10V
Modbus : RS A - RS B
0-10V analog input : 0..10V - COM
Sensor supply : +10V - COM
Slave control : OUT - GND
Alarm relay: COM - NC (SELV)

The device is compatible with Modbus protocol RTU. Please read additional instructions about Hidria EC Modbus parameters.

WARNING : Leakage current exceeds 3.5mA.

Short circuit rating: <10kA .

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

6 / 10

Summary of Contents for 0318-4-1006

Page 1: ...ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL DATA This document contains instructions and information for the operation installation connection use and maintenance of the product Be sur...

Page 2: ...rm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance is not intended to be built as a part...

Page 3: ...not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be permanently co...

Page 4: ...ensing Max pressure 250 Pa ErP DATA Overall Efficiency Effes 54 3 Installation category A Efficiency category static Efficiency grade N 57 7 Variable speed drive INTEGRATED Power Input Pelec 2917 9 W...

Page 5: ...juries the height and the diameter of inlet cone must be appropriate dimensions To lift the device with lifting devices use the hangers provided for this purpose as shown on figure below Always use su...

Page 6: ...ng plug must remain in the gland Connection box screws have to be tightened with torque of 2 0Nm 2 5Nm Secure connection cable to the fan guard grill or to the motor holder with cable fasteners so tha...

Page 7: ...but the highest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In o...

Page 8: ...correct value the motor will restart automatically In the specific case the undervoltage protection may switch off the fan to stand by mode for example fan running or testing at high pressure drop an...

Page 9: ...in circuit of electronics windings never try to repair the fan but replace it with new one or and return defected fan to the manufacturer for repair or replacement ALARM RELAY DIAGNOSTICS Alarm relay...

Page 10: ...protection grill Do not apply any force for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transp...

Reviews: