USER'S GUIDE R18 AXIAL FAN , Iss: 6.05.2021

05

SPEED CONTROL DIAGRAM

Rotation speed of a variable speed fan can be controlled by various signals:

- Linear voltage input (0-10V) or current input (4-20mA) or PWM input (PWM duty cycle 0-100%).
- MODBUS RTU protocol (Additional information are in documentation "Hidria EC Modbus parameters".

Linear voltage input is the most common and it is described below. The current input is also widely used, where long cables are necessary. PWM input
is used for electromagnetic noisy environments. PWM signal must be in square form with polarity the same as for linear voltage input (see connection
diagram). PWM duty cycle 0-100% correspond to 0-10V linear voltage input if the amplitude of the PWM voltage is Vp=10V. Amplitude of PWM signal
must not exceed 12Vp.

LINEAR VOLTAGE INPUT:

Linear input is factory adjusted to fit the customer’s sensor or other speed control reference. The input characteristic can be factory adjusted in terms of
increasing input sensitivity or attenuation. 

For example: An air-cooled condenser is using a pressure sensor 0-20Bar => 0-10V, but the highest system pressure reached at maximum load is
16Bar => 8V. For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage. In order
to achieve that, we need to adjust the input characteristic in a way the picture shows. 

1.0V

1,2V

Input voltage (0

10V)

Fa

n

 s

p

e

e

d

HYSTERESIS

100%

1.2V

10V

Input voltage (0

10V)

Fan speed

CONTROL DIAGRAM

8V

adjusted

input curve

100%

1.2V

10V

Input voltage (0

10V)

Fan speed

INPUT CHARACTERISTIC ADJUSTMENT

0

200

400

600

800

1000

1200

Fa

n

 r

o

ta

ti

o

n

a

sp

e

e

d

 (R

P

M

)

Input Voltage (0...10 V)

SPEED CONTROL DIAGRAM

1.2 V

10 V

5 V

O

N

/O

F

F

 

H

Y

S

T

E

R

E

S

IS

D

=

0

.2

V

In order to prevent cycling from standby to run mode or run to standby 
mode a small hysteresis is implemented. The default value is 
approximately 200mV. 
Hysteresis can be factory-adjusted in order to achieve customer 
requirements.

Linear voltage input (0-10V DC) can be used as 0 (4)-20mA current 
input with an additional resistor of 500 Ohms between GND and 0-10V 
connection.

Speed of a fan increases linearly with input voltage. 

The fan operates in two different modes:
0-1.2 V…… Standby or stop mode
1.2-10 V….. Run mode
1.0-1.2V .....Hysteresis

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

7 / 10

Summary of Contents for 0318-4-1006

Page 1: ...ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL DATA This document contains instructions and information for the operation installation connection use and maintenance of the product Be sur...

Page 2: ...rm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance is not intended to be built as a part...

Page 3: ...not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be permanently co...

Page 4: ...ensing Max pressure 250 Pa ErP DATA Overall Efficiency Effes 54 3 Installation category A Efficiency category static Efficiency grade N 57 7 Variable speed drive INTEGRATED Power Input Pelec 2917 9 W...

Page 5: ...juries the height and the diameter of inlet cone must be appropriate dimensions To lift the device with lifting devices use the hangers provided for this purpose as shown on figure below Always use su...

Page 6: ...ng plug must remain in the gland Connection box screws have to be tightened with torque of 2 0Nm 2 5Nm Secure connection cable to the fan guard grill or to the motor holder with cable fasteners so tha...

Page 7: ...but the highest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In o...

Page 8: ...correct value the motor will restart automatically In the specific case the undervoltage protection may switch off the fan to stand by mode for example fan running or testing at high pressure drop an...

Page 9: ...in circuit of electronics windings never try to repair the fan but replace it with new one or and return defected fan to the manufacturer for repair or replacement ALARM RELAY DIAGNOSTICS Alarm relay...

Page 10: ...protection grill Do not apply any force for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transp...

Reviews: