IC100CX SERVICE MANUAL                                                                                                                      

 
 

 

 Manual IC100CX GB                                                                                     

 

 

 

Page 7 di 20  

Pb3 probe has to be configured to use a pressure transducer. 
 
When the evaporator condenser pressure is greater than  CO21 set point, a compressor 
(if two compressors are working) or the capacity control (in case of one compressor with 
capacity step) is switched off. 
When only one compressor is working or only the capacity step is active, the function 
has not effect on the regulation. 
The lower display shows “ACUn” alternated to default visualization. 
 
When the evaporator condenser pressure falls below CO21  – CO22, the function is 
disabled and, if required for the regulation, the previously shut down 

 

compressor/capacity step can be re-inserted. 
 
Note 
When the unloading function is active, to avoid a prolonged working time in this 
condition, if the evaporator condenser pressure is lower than CO21 set point and higher 
than CO21 – CO22 for a time of CO25, the function is disabled. 
CO25 delay time starts when the evaporator condenser pressure is lower than CO21 set 
point.  
 

Low pressure in heat pump mode  

The function allows the machine to operate in case of low outside temperature (start-up 
in winter with ice-covered batteries), to avoid possible low pressure alarm. 
Pb3 probe has to be configured to use a pressure transducer. 
 
When the evaporator condenser pressure is lower than  CO23 set point, a compressor 
(if two compressors are working) or the capacity control (in case of one compressor with 
capacity step) is switched off. 
When only one compressor is working or only a capacity step is active, the function has 
not effect on the regulation. 
The lower display shows “ACUn” alternated to default visualization. 
 
When the evaporator condenser pressure is greater than  CO23 + CO24, the function is 
disabled and, if required for the regulation, the previously  shut down 
compressor/capacity step can be re-inserted. 
 
Note 
When the unloading function is active, to avoid a prolonged working time in this 
condition, if the evaporator pressure is higher than CO23 set point and lower than CO23 
+ CO24 for a time of CO25, the function is disabled. 
CO25 delay time starts when the evaporator pressure is higher than CO23 set point.  
 
 

B

OILER 

F

UNCTION 

 

The boiler function can be used for heating (Ar20=1) or for  support the heating function 
(Ar20=0).  
To enable the function is necessary: 

 

unit configured in Heat Pump mode 

 

Pb4 configured as external air probe (CF07=3) 

 

Heating Integration Control Ar20=0 

Anti-freeze/support heater 1: 
Heather ON if: 

 

outside air temperature < Ar21 for more than Ar23 time 

 

regulation probe < Heating set point or real Heating set poinf (if Energy saving or 

Dynamic set point or function for units without water storage tank are enabled) 

 
Ar23 delay time starts when outside temperature falls below Ar21 set point. 
If outside temperature exceeds the Ar21 + Ar22 when the counting of Ar23 is running, 
the boiler function is not enabled and the Ar23 time is re-loaded. 
 
Heather OFF if: 

 

outside air temperature > Ar21 + Ar22 

 

regulation probe > Heating set point or real Heating set poinf (if Energy saving or 

Dynamic set point or function for units without water storage tank are enabled) 

 
If outside air temperature falls below the Ar25 set point the compressors are switched 
off; when outside air temperature is higher than Ar25 set point + the Ar26 differential the 
compressors are switched on. 
 
Anti-freeze/support heater 2: 
Heather ON if: 

 

outside air temperature < Ar21 for more than Ar23 + Ar24 time 

 

regulation probe < Heating set point – (ST04 / 2) or real Heating set point – (ST04 / 2) 

(if Energy saving or Dynamic set point or function for units without water storage tank 
are enabled) 

 

Ar23 delay time starts when outside temperature falls below Ar21 set point. 
Ar24 delay time starts when Ar23 is elapsed. 
If the outside temperature exceeds Ar21 + Ar22 when the counting of Ar23 is running, 
the boiler function is not enabled and the Ar23 time is re-loaded. 
 
Heather OFF if: 

 

outside air temperature > Ar21 + Ar22 

 

regulation probe > Heating set point or real Heating set poinf (if Energy saving or 
Dynamic set point or function for units without water storage tank are enabled) 

 
If the outside air temperature falls below the Ar25 set point the compressors are 
switched off; when outside air temperature is higher than Ar25 set point + the Ar26 
differential, the compressors are switched on. 

Heating Control Ar20=1 

Anti-freeze/support heater 1: 
Heather ON if: 

 

outside air temperature < Ar21 for more than Ar23 time 

 

regulation probe < Heating set point or real Heating set poinf (if Energy saving or 

Dynamic set point or function for units without water storage tank are enabled) 

 
Ar23 delay time starts when outside temperature falls below Ar21 set point. 
When the heather is switched on, the compressor and condenser fans are switched off. 
If the outside temperature exceeds Ar21 + Ar22 when the counting of Ar23 is running, 
the boiler function is not enabled and the Ar23 time is re-loaded 
 
 
Heather OFF if: 

 

outside air temperature > Ar21 + Ar22 

 

regulation probe > Heating set point or real Heating set poinf (if Energy saving or 

Dynamic set point or function for units without water storage tank are enabled) 

 
If the outside air temperature exceeds the Ar21 + Ar22 the heater is switched off and the 
compressor and fans are switched on (if the heat regulator calls for it). 
 
Anti-freeze/support heater 2: 
Heather ON if: 

 

outside air temperature < Ar21 for more than Ar23 + Ar24 time 

 

regulation probe < Heating set point – (ST04 / 2) or real Heating set poinf – (ST04 / 2) 
(if Energy saving or Dynamic set point or function for units without water storage tank 
are enabled) 

 
Ar23 delay time starts when outside temperature falls below Ar21 set point. 
Ar24 delay time starts when Ar23 is elapsed. 
If the outside temperature exceeds Ar21 + Ar22 when the counting of Ar23 is running, 
the boiler function is not enabled and the Ar23 time is re-loaded. 
 
Heather OFF if: 

 

outside air temperature > Ar21 + Ar22 

 

regulation probe > Heating set point or real Heating set poinf (if Energy saving or 

Dynamic set point or function for units without water storage tank are enabled) 

 

M

AINTENANCE 

F

UNCTION

 

The maintenance warning is activated if the compressor 1, compressor 2,  evaporator 
water pump / supply fan (air/air unit), condenser water pump have worked for a time set 
by parameter (CO14, CO15, CO16 and CO28). 
The maintenance alarm code are: 
A13=comp.1, A14=comp.2, A15=water pump or supply fan, A20=condenser pump.  
The maintenance warning is only a visual signaling and  does not influence the 
regulation. 
To reset the warning is necessary to set the operating hours at zero value in the menù 
function. 
 

 

B

LACK 

O

UT

 

After a black-out: 
1.

 

the controller restarts from the pervious status. 

2.

 

The defrost cycle is stopped. 

3.

 

All the working time delay will be reloaded. 

Summary of Contents for iCHiLL 100CX

Page 1: ...IC100CX SERVICE MANUAL Manual IC100CX GB Page 1 di 20 iCHiLL 100CX Service Manual ...

Page 2: ...ch is activated When the pump is OFF the led is on flashing to indicate the correct status of the digital input On if at least one water pump is on On if evaporator fans are activated On if a compressor is on On flashing during the delay time for compressor activation On if open collector output is active On if the controller is on in Heat or Cool mode On in case of Low pressure alarm or High pres...

Page 3: ...r digits yellow color configurable by parameter CF43 PB1 PB2 PB3 PB4 Set point parameter value working set point real set point modified from dinamic set point Energy saving or function for units without water storage tank Hysteresis RTC Machine status the display visualizes chiller set point when the unit is on and in chiller mode heating set point when the unit is on and in heat pump mode and OF...

Page 4: ... o when a parameter label is displayed or wait 15s time out without pushing any keys NOTE The new parameter value is also confirmed if after changing it no SET key is pressed for the time out to exit ATTENTION CF parameters Configuration parameters can be modified only if the controller is in OFF digital input or STD BY HOW TO CHANGE THE PASSWORD To change the password you must know the previous v...

Page 5: ...nd upper display shows the value push SET key again when Energy Saving is enabled the lower display shows SEtS Energy saving setpoint and upper display shows the value when Dynamic Set is enabled the lower display shows SEtd dynamic set point and upper display shows the value when the function for units without water storage tank is enabled the lower display shows Setr real set point and upper dis...

Page 6: ...ferential differential chiller Par ST14 CO01 compressor working time x Par ST16 10 Compressor working time is in sec x 10 The function for units without water storage tank is compatible with Energy Saving function or with the Dynamic set point Visualization of the set point on the display Chiller with energy saving or dynamic set point enabled push SET button once SetC set point value from paramet...

Page 7: ...higher than Ar25 set point the Ar26 differential the compressors are switched on Anti freeze support heater 2 Heather ON if outside air temperature Ar21 for more than Ar23 Ar24 time regulation probe Heating set point ST04 2 or real Heating set point ST04 2 if Energy saving or Dynamic set point or function for units without water storage tank are enabled Ar23 delay time starts when outside temperat...

Page 8: ...rm A10 Compressor 2 thermal protection alarm A11 Condenser fan thermal protection alarm A12 Defrost error alarm A13 Compressor 1 maintenance warning A14 Compressor 2 maintenance warning A15 Water pump or supply air fan air air maintenance warning A16 High temperature evaporator inlet water A17 Thermal protection alarm for evaporator water pump supply fan A18 Thermal protection alarm for condenser ...

Page 9: ...tank Parameter Description Min Max Meas Resolution ST10 Chiller unit without water storage tank 0 function disabled 1 function activated 0 1 ST11 Minimum temperature Set point for outlet water in chiller mode unit without water storage tank 50 0 58 110 230 C F Dec int ST12 Maximum temperature Set point for outlet water in HP function unit without water storage tank 50 0 58 110 230 C F Dec int ST13...

Page 10: ... control 2 4 20mA for condensing pressure 3 4 20ma for Dynamic Set point 4 NTC temperature for anti freeze alarm water water 5 NTC high temperature probe of system inlet water 6 0 5V for condensing pressure 0 6 CF07 Pb4 configuration 0 Probe not enabled 1 NTC condensing control 2 Multifunction digital input 3 External air temperature 4 NTC temperature for anti freeze alarm water water 5 NTC temper...

Page 11: ...thermal protection alarm 14 Condenser flow switch alarm 15 not used 0 15 CF11 Pb4 configuration in digital input mode 0 1st compressor thermal protection 1 Condenser fan thermal protection 2 Evaporator flow switch alarm 3 Remote On off 4 Cooling Heating 5 2nd compressor thermal protection 6 2nd compressor or step request Motocondensing unit 7 End defrost 8 Energy Saving 9 Anti Freeze alarm 10 1st ...

Page 12: ...integer CF26 Pb3 Offset 12 0 21 12 0 174 12 0 21 12 0 174 C F Bar Psi Decimal Integer Decimal integer CF27 Pb4 Offset 12 0 21 12 0 21 C F Decimal integer CF28 Chiller or Heat Pump configuration 0 chiller and heat pump selected by keyboard 1 chiller and heat pump selected by digital input 2 chiller and heat pump selected by probe 3 only chiller unit 4 only heat pump unit 0 4 CF29 Automatic Changeov...

Page 13: ...pump 0 10 CF42 Switching time of reversing valve when the compressor is switched off 0 250 CF43 Default viewing of lower display of the controller 0 PB1 visualization 1 PB2 visualization 2 PB3 visualization 3 PB4 visualization 4 Real working set point set point modified from Energy Saving Dynamic set point function for units without water storage tank 5 Unit status 6 Clock 7 No visualization 8 Wok...

Page 14: ...5 C F Decimal integer ES12 Energy saving setpoint offset in heat pump 30 0 54 30 0 54 C F Decimal integer ES13 Energy saving differential in heat pump 0 1 0 25 0 45 C F Decimal integer Pr2 Password value 0 999 Compressor parameters Parameter Description Min Max Meas Resolution CO01 Minimum ON time 0 250 Sec 10Sec CO02 Minimum OFF time 0 250 Sec 10Sec CO03 ON delay time between two compressors or C...

Page 15: ...0 CO33 Minimum speed of modulating pump in operation with enabled compressor Heat Pump 30 100 CO34 Speed of modulating pump in operation with enabled compressor 30 100 CO35 Set point modulating pump in chiller mode evaporator outlet temperature 50 0 58 110 230 C F Dec int CO36 Temperature control band for the modulating pump in chiller function 0 0 0 25 0 45 C F Dec int CO37 Delay for switching of...

Page 16: ... function 30 100 Hot Start Function Parameter Description Min Max Meas Resolution FA25 Hot Start Setpoint 50 0 58 110 230 C F Decimal integer FA26 Hot Start differential 0 1 0 25 0 45 C F Decimal integer Pr2 Password 0 999 Anti freeze Heater parameters Parameter Description Min Max Meas Resolution Ar01 Minimum value of Anti Freeze Setpoint 50 0 58 Ar03 C F Decimal integer Ar02 Maximum value of Ant...

Page 17: ... 0 1 0 25 0 45 C F Dec int Anti freezer alarm in HP function Ar27 Anti freeze alarm set point in heat pump mode Ar01 Ar02 C F Dec int Ar28 Anti freeze alarm differential in heat pump mode 0 0 25 0 45 C F Dec int Evaporator water pump functioning condenser of ambient probe Ar29 Evaporator condenser water pump set point with external temperature regulation 50 0 58 110 230 C F Dec int Ar30 Evaporator...

Page 18: ...1 hour 0 16 AL03 Low pressure alarm with off compressor 0 Not enabled when compressor Off 1 Enabled when compressor Off 0 1 AL04 Water flow Supply fan thermal protection alarm delay after water pump supply air fan starting 0 250 Sec AL05 Maximum duration of the flow switch alarm before it becomes manual and blocks the water pump 0 250 Sec AL06 Water flow Supply fan thermal protection input activat...

Page 19: ...f system inlet high temperature alarm interventions per hour 0 16 AL28 Condenser water flow alarm delay time 0 250 Sec AL29 Maximum duration of the flow switch alarm before it becomes manual and blocks the water pump 0 250 Sec AL30 Minimum activation time for water flow alarm 0 250 Sec AL31 Minimum time with inactive water flow input after alarm event 0 250 Sec AL32 Condenser flow switch alarm con...

Page 20: ...ion relays Pb1 Pb2 Pb4 NTC probe or digital input Pb3 pressure trasducer Tk output for external fan speed controller MF o c out multifunction open collector output for external relay 1 4 Model with 5 internal relays and ratiometric pressure trasducer Pb3 MF ID1 MF ID2 MF ID5 multifunction digital inputs ID3 high pressure digital input ID4 low pressure digital input MF RL2 MF RL3 MF RL4 MF RL5 mult...

Reviews: