MTEC.6500.GB-F-1 Operation and maintenance manual SDA series English
SDA
6ZLPPLQJSRROGHKXPLGL¿HUV
4.13 Desuperheater connection (RP01)
7KHGHVXSHUKHDWHULVIDFWRU\¿WWHG,WLVFRQWUROOHGE\DFLUFXODWLRQSXPSQRWVXSSOLHGGLUHFWO\PDQDJHGE\WKHFRQWUROFDUG
Water pool return
Pool water disinfection treatment
Pool water pump
Pool water disinfection dosing system
Pool water valve
Pool water heating system
3RROZDWHU¿OWHU
To the pool water heating system (Boiler, heat pump, etc.)
'HKXPLGL¿HU
Pool water valves adjustment set
Partial heat recovery
Water pool supply
7KHSDUWLDOKHDWUHFRYHU\FRLOPXVWDOZD\VEHLQVWDOOHGGRZQVWUHDPRIWKHZDWHU¿OWHUDQGXSVWUHDPRIWKHZDWHU
disinfection treatment in the pools hydraulic circuit. The positioning of the heat exchanger upstream of the disin-
fection treatment is important because prolonged exposure to high concentrations of disinfectants chemicals can
cause irreparable damage to the heat recovery coil. Downstream of the disinfection system has generally much
higher concentration of disinfectants than in the pool. It’s also important for the partial heat recovery coil to be
SRVLWLRQHGXSVWUHDPRIWKH¿OWHUVRWKDWDQ\GHEULVIURPWKHSRROGRQRWSDVVLQWRWKHFRLO:KLFKFDQFDXVHSRRU
performance of the coil and damage!
4.13.1 Partial heat recovery hydraulic connections (option)
Desuperheater
connections