SRH
Swimming Pools Dehumidifiers
MTSRHGB
25
REV.072008
SAFETY DEVICE
DEFROSTING
The frost on the coil, obstructs the air flow, reduces the available exchange area and consequently the heating capacity. This can
damage seriously the system. All the units are equipped of a control which defrost automatically the heat exchanger if there is the
need. This control provides a temperature probe (defrost thermostat) on the heat exchanger. When the microprocessor feel the need
to act the defrost cycle (according to parameters set in advance), it does it (yellow led on)switching the compressor off, while the fan
continues working. At the end of the defrost cycle, the dripping time starts(the green led blinks fastly)
HIGH PRESSURE SWITCH
The high pressure switch stops the unit when “condensing pressure ” exceed the pre-set value. The reset is manual (you need to
press the button on the pressure switch) and it can be carried out only when the pressure is under the value indicated by the
differential set (see table below).
LOW PRESSURE SWITCH
The low pressure switch stops the unit when the suction pressure goes lower than the pre-set value. The reset is automatic and it’s
possible only when the pressure is over the value indicated by the differential set (see table below).
DEFROST THERMOSTAT
It’s a device which signals to the electronic control, the necessity to make the defrost cycle. Once the defrost cycle is activated, the
defrost device determines also its conclusion.
SAFETY DEVICE SETTING
Device
Set-point
Differential
Reset type
Anti-freeze thermostat
°C
1 3
AUTOM.
High pressure switch
Bar
26 7,7
MANUAL
Low pressure switch
Bar
1,7 1
AUTOM.
ELECTRICAL DATA
Power supply
V/~/Hz
400 / 3 / 50
Control board
V/~/Hz
24 / 1 / 50
Auxiliary circuit
V/~/Hz
230 / 1 / 50
Fans power supply
V/~/Hz
400 / 3 / 50
INSPECTION
When installing or servicing the unit, it is necessary to strictly follow the rules reported on this manual, to conform to all the
specifications of the labels on the unit, and to take any possible precautions of the case. Not observing the rules reported on this
manual can create dangerous situations. After receiving the unit, immediately check its integrity. The unit left the factory in perfect
condition; any eventual damage must be questioned to the carrier and recorded on the Delivery Note before it is signed. HIDROS
must be informed, within 8 days, of the extent of the damage. The Customer should prepare a written statement of any severe
damage.
Summary of Contents for SRH Series
Page 1: ...SWIMMING POOLS DEHUMIDIFIERS SRH SERIES TECNICAL MANUAL ...
Page 2: ...SRH Swimming Pools Dehumidifiers MTSRHGB 2 REV 072008 ...
Page 3: ...SRH Swimming Pools Dehumidifiers MTSRHGB 3 REV 072008 ...
Page 4: ...SRH Swimming Pools Dehumidifiers MTSRHGB 4 REV 072008 ...
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......