ELECTRICAL CONNECTIONS
It must be verified that electric supply is corresponding to the unit electric nominal data (tension, phases, frequency) reported on the
label in the front panel of the unit. Power connections must be made in accordance to the wiring diagram enclosed with the unit and
in accordance to the norms in force. Power cable and line protection must be sized according to the specification reported on the
form of the wiring diagram enclosed with the unit
WARNING: The line voltage fluctuations can not be more than ±5% of the nominal value, while the voltage
unbalance between one phase and another can not exceed 2%. If those tolerances should not be
respected, please contact our Company.
WARNING: Electric supply must be in the limits shown: in the opposite case warranty will terminate
immediately. Before every operation on the electric section, be sure that the electric supply is
disconnected.
START UP
Before start-up
•
Check that all power cables are properly connected and all terminals are hardly fixed.
•
The voltage at the phase R S T is the one shown in the unit labels.
•
Check that there is not any refrigerant leakage.
•
Check that crankcase heaters are powered correctly.
•
Check that all water connections are properly installed and all indications on unit labels are observed.
•
The system must be bleed off in order to eliminate any air.
•
Before proceeding to start up check that all the cover panels are re-located in the proper position and locked with fastening
screws.
WARNING: Crankcase heaters must be powered at least 12 hours before start up by closing the main
switch (heaters are automatically supplied when main switch is closed). The crankcase heaters are
working properly if after some minutes the compressor crankcase temperature is about 10÷15°C
higher than ambient temperature..
Start-up
Before to proceed to start up close the main switch
.
Units are provided with 2 types of microprocessor controls that manage all the various functions of the unit. The functions described
below are applied both for local board control and/or remote panel control.
The procedure to start up the unit depends on the type of control installed; please refer to the following pages.
CONTROL PANELS
All SRH units can be supplied with 2 kind of controls:
•
Basic control
•
Advanced control
Summary of Contents for SRH Series
Page 1: ...SWIMMING POOLS DEHUMIDIFIERS SRH SERIES TECNICAL MANUAL ...
Page 2: ...SRH Swimming Pools Dehumidifiers MTSRHGB 2 REV 072008 ...
Page 3: ...SRH Swimming Pools Dehumidifiers MTSRHGB 3 REV 072008 ...
Page 4: ...SRH Swimming Pools Dehumidifiers MTSRHGB 4 REV 072008 ...
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......