MTEC.3800.GB-B-1 Operation and maintenance WSA series English
WSA
Water chiller
4.22 Electric connections
4.22.1 Remote wiring connections (compulsory)
All terminals referred to in the explanations below will be found on the terminal board inside the electrical box. All electric connections
mentioned below have to be made by the installer, on site.
REMOTE ON / OFF
To switch the unit on or off remotely, the cable jumper connected across terminals 1 and 2 must
be replaced with a switch.
Contact closed, unit ON,
Contact open, unit OFF.
REMOTE SUMMER / WINTER CHANGE OVER
To remotely switch the unit from heating to cooling, the cable jumper connected across termi-
nals 13 and 43 must be replaced with a switch.
Contact closed, unit in Winter mode,
Contact open, unit Summer mode.
REMOTE GENERAL ALARM
For remote display of a general alarm, connect the visual or audible device between terminals
90-91-92.
Contacts 90/91 NC (Normally closed)
Contacts 91/92 NO (Normally opened)
REMOTE CONTROL PANEL
The remote control panel replicates all of the functions on the main controller panel and can
be connected up to a maximum distance of 50 meters from the unit. The panel has to be
connected to the unit by 2 wires having diameter 0.75 mm2. The power supply cables must be
separated from the remote control panel wires, in order to avoid interference. The control panel
has to be connected to the ter and –. The control panel cannot be installed in an area
subject to excessive vibration, corrosive gases, is a dirty environment or has a high humidity
level. The ventilation openings must not be blocked.
USER CIRCUIT FLOW SWITCH (SFW1)
This is used to protect the unit if there is a low water flow rate in the user circuit. It is factory
fitted across terminals 14 and 43.
The numbering of the terminals may change without notice. For their connection is mandatory to refer to the wiring
diagram supplied along with the unit.