MTEC.3800.GB-B-1 Operation and maintenance WSA series English
WSA
Water chiller
6.4.1 Adjustable parameters
The adjustable set points that can be modified by the end user are:
Label
Function
Adjustment limit
Default value
SEt H
Heating set-point
20÷55°C
40°C
SEt C
Cooling set-point
10÷23°C
12°C
SD02
Set point compensation
0÷15°C
10°C
PAS
Password
(Contact the company)
The units are supplied with a very sophisticated control system with many other parameters that are not adjustable
by the end user; these parameters are protected by a manufacturer password.
By pressing the
key the user has the possibility to display many parameters.
Scroll the list of the parameters using the
,
keys, then press the
key to display the required one.
In this menu it is only possible to display the parameters, it is not possible to change any value. The parameter list is:
Display
List
Symbol Meaning
ALrM
Alarm List
ALrM
See following paragraph
ALOG
Alarm history
ALOG
See following paragraph
HouR
Main components working hours
C1HR
C2HR
PFHR
PCHR
Working hours compressor 1
Working hours compressor 2 (only models with 2 com-
pressors)
Working hours user water pump
Working hours domestic hot water pump
DEF
(Not used)
dF1
Countdown (in seconds) to the next defrost cycle; the
countdown is active if the defrost led
is blinking. In
case the defrost led is off the defrost cycle is not required.
During the defrost cycle the defrost led is ON.
6.5 Parameters list
Pressing and releasing one of the keys; the buzzer is switched off, even if the alarm condition remains in place.
Press the
key (the menu
AlrM
appears at the bottom right of the display). Press the
key to display the alarm event.
In case of multiple alarms use the using the
,
keys, to scroll through the list of the active alarms.
There are two types of alarms:
Reset alarms:
RST
label appears on the upper part of the display. In this case press the
key to reset.
Non reset alarm:
nO
label appears on the upper part of the display. In this case the alarm is permanent; contact Hidros technical support.
6.6 Acoustic signal silencing
6.7 Alarm Reset
Press the
key, then the
,
keys, to scroll through the menus, when ALOG label appears in the bottom part of the
display, press
. To scroll the list of alarms use the
,
keys.
6.8 Display alarm history