background image

ISO 9001 2008

The World’s Source for High Voltage Test Equipment

MADE IN THE USA

High Voltage, Inc. 

• 

hvinc.com 

• 

p. 518.329.3275 

• 

f. 518.329.3271 

• 

31 County Route 7A 

• 

Copake, NY 12516 USA

VLF E Series VLF hook up 

and control with E-Link

Summary of Contents for VLF E Series

Page 1: ...8 The World s Source for High Voltage Test Equipment MADE IN THE USA High Voltage Inc hvinc com p 518 329 3275 f 518 329 3271 31 County Route 7A Copake NY 12516 USA VLF E Series VLF hook up and control with E Link ...

Page 2: ...e NY 12516 USA Disclaimer This guide for the High Voltage Inc E Series of VLF hipots are meant to be for reference only The instructions are intended to be clear and simple but the operator must be trained and qualified according to the established procedures required for the use of this type of equipment Before operating a VLF Hipot consult the operators manual ...

Page 3: ...2008 The World s Source for High Voltage Test Equipment MADE IN THE USA High Voltage Inc hvinc com p 518 329 3275 f 518 329 3271 31 County Route 7A Copake NY 12516 USA E Series VLF Hipot Hook Up VLF 34E VLF 65E ...

Page 4: ...age Inc hvinc com p 518 329 3275 f 518 329 3271 31 County Route 7A Copake NY 12516 USA Step 1 Ground VLF Hipot Connect the ground stud of the VLF to station ground concentric neutral of the cable under test and or low side of your test object VLF 34E Shown Station Ground Neutral or Low Side ...

Page 5: ...High Voltage Test Equipment MADE IN THE USA High Voltage Inc hvinc com p 518 329 3275 f 518 329 3271 31 County Route 7A Copake NY 12516 USA Step 2 Install High Voltage Output Cable Install shielded output cable tighten ring lug until snug ...

Page 6: ...uipment MADE IN THE USA High Voltage Inc hvinc com p 518 329 3275 f 518 329 3271 31 County Route 7A Copake NY 12516 USA Step 3 Connect To the Test Object Connect the Alligator Clip from the High Voltage Output Cable to cable or high side of device under test ...

Page 7: ... County Route 7A Copake NY 12516 USA Step 4 Check the VLF Measurement Source is set to VLF 34E or VLF 65E 1 Push the blue button to enter Advanced screen 2 Scroll down to Measurement Source 3 Push down on the encoder or press the green button 4 Choose VLF 34E or VLF 65E depending on model 5 Push down on the encoder or press the green button ...

Page 8: ...e desired Waveform 1 Sinewave 2 Square Wave 3 Positive DC 4 Negative DC 3 Choose the desired output frequency 0 1Hz 0 01Hz 4 Choose voltage step 1 1 Set up first test voltage per IEEE 400 2 2013 2 Set duration for 30 minutes to 1 hour 3 Repeat for step 2 through 5 if need 5 Choose desired Fault condition 1 Overload on Arc to have VLF power down if failure occurs 2 Burn on Arc to have VLF condition...

Page 9: ...08 The World s Source for High Voltage Test Equipment MADE IN THE USA High Voltage Inc hvinc com p 518 329 3275 f 518 329 3271 31 County Route 7A Copake NY 12516 USA Control of VLF and Tan Delta via E Link with PC ...

Page 10: ...e Inc hvinc com p 518 329 3275 f 518 329 3271 31 County Route 7A Copake NY 12516 USA Step 6 Insert the green USB Xbee Antenna into PC 1 Plug green USB Xbee Antenna into PC 2 Install the drivers for the Xbee Antenna 3 Download via the Internet or 4 Download via the red or black HVI flash drive ...

Page 11: ...SA Step 7 Establish Wireless Connection Between VLF and PC via the Xbee Protocol 1 Install the E Link software from the red HVI flash drive 2 Open the E Link software 3 Click on Settings 4 Click on the Communications tab 5 Click the Auto Detect button 6 The software should automatically assign a serial port 7 Click Close 8 If you have issues please contact factory hvinc com ...

Page 12: ... World s Source for High Voltage Test Equipment MADE IN THE USA High Voltage Inc hvinc com p 518 329 3275 f 518 329 3271 31 County Route 7A Copake NY 12516 USA Step 8 Test Setup using the E Link Software Click Run Test ...

Page 13: ...2 Choose your desired Waveform 1 Sinewave 2 Square Wave 3 Positive DC 4 Negative DC 3 Choose your output frequency 1Hz to 01Hz 4 Choose voltage step 1 1 Set up first test voltage per IEEE 400 2 2013 2 Set duration for 30 minutes to 1 hour 3 Repeat for step 2 through 5 if need 5 Choose desired Fault condition 1 Overload on Arc to have VLF power down if failure occurs 2 Burn on Arc to have VLF condi...

Page 14: ...ent MADE IN THE USA High Voltage Inc hvinc com p 518 329 3275 f 518 329 3271 31 County Route 7A Copake NY 12516 USA Thank you for viewing if you have any questions please contact High Voltage Inc or your local High Voltage Inc Sales Representative Thank You from ...

Reviews: