O P E R A T O R M A N U A L
19
19.
Maintain the BURN mode voltage until the cable has sufficiently burned to a low impedance
fault, as indicated on the unit Kilovoltmeter and conventional fault locating techniques can
be used.
20.
After the test is complete, depress the HIGH VOLTAGE control in LOWER position,
allowing the load to return to zero and the unit to cycle for about 3 more cycles prior to
depressing the HV OFF pushbutton. Allowing the unit to cycle for some time allows for the
complete discharge of the load and avoiding the normal self-recharge that capacitive loads
will exhibit.
21.
Prior to removing the output cable from the load, observe that the output voltmeter is
at zero, and then use a GROUND STICK to positively ground the test sample
.