3NDML-NRG
ELECTRICAL DATA
09/13
Lighting Data
Case
Length
Lights
Per Row
Light
Length
Clearvoyant LED Lighting
(Per Light Row)
Standard Power
(Cornice or Shelf)
High Power
(Cornice)
120 Volts
120 Volts
Amps
Watts
Amps
Watts
6'
2
3'
0.14
16.6
0.25
29.8
Electrical Data
Case
Length
Fans
Per Case
High Effi ciency
Fans
Anti-Condensate
Heaters
120 Volts
120 Volts
Amps
Watts
Amps
Watts
6'
2
0.38
43
- - -
1
- - -
Defrost Controls
Defrosts
Per Day
Run-Off
Time (min)
Electric Defrost
Timed-Off Defrost
Hot Gas Defrost
Fail-Safe
(min)
Termination
Temp (°F)
Fail-Safe
(min)
Termination
Temp (°F)
Fail-Safe
(min)
Termination
Temp (°F)
6
6 - 8
- - -
- - -
42
42
- - -
- - -
Guidelines & Control Settings
Multi-Deck Merchandiser with Synerg-E
™
4', 6', 8' & 12' (Beverage / Dairy / Deli / Produce)
3NDML-NRG
Application
2
BTUH/ft
Superheat
Set Point @ Bulb
(°F)
Evaporator
3
(°F)
Discharge
4
Air
(°F)
Discharge
5
Air Velocity
(FPM)
Conventional Parallel
Dairy / Deli / Cut Produce
1177
1232
6 - 8
28
34
350
Produce / Beverage
1059
1091
6 - 8
32
37
350
1 NOTE: "- - -" indicates that feature is not an option on this case model.
2 BTUH/ft notes:
- Listed BTUH/ft indicate unlighted shelves. For LED lighting, add 36 BTUH per 4' lighted shelf and 27 BTUH per 3' lighted shelf to determine Total Lighting BTUH Load, then divide the
Total Lighting BTUH Load by the length of the case. For T8 lighted shelves (see Appendix D) and 3rd row lighting, add 92 BTUH per 4' lighted shelf and 69 BTUH per 3' lighted shelf to
determine Total Lighting BTUH Load, then divide the Total Lighting BTUH Load by the length of the case.
- Add 132 BTUH/ft when aftermarket merchandising accessories are utilized to determine the total BTUH load.
3 Listed evaporator temperature indicates unlighted shelves. For lighted shelves and/or aftermarket merchandising accessories, reduce the listed evaporator temperature by
2°F
.
4 Conventional Discharge Air Control – Recommended Settings: Cut-In Temp = Discharge Air + 2°F; Cut-Out Temp = Discharge Air - 2°F
5 Average discharge air velocity at peak of defrost.
A1
Summary of Contents for 3NDML-NRG
Page 16: ...BLUE WHITE BLACK 3NDML WIRING DIAGRAM B2 ...
Page 19: ...SEISMIC BRACKET 5 D2 ...
Page 20: ...SEISMIC BRACKET 7 D3 ...
Page 21: ...SEISMIC BRACKET 11 D4 ...
Page 22: ...SEISMIC BRACKET 15 D5 ...