OMHAC415-120PX 

 

 

SAFETY   CONSIDERATIONS  

1. The   unit   should   only   be   operated   by   competent   electrical   engineers   who   are  

completely   familiar   with   the   operation   and   specification   of   the   load   bank. 

 

2. The   equipment   is   designed   for   AC   operation   only   and   therefore   must   not   be  

used   on   DC   loads   such   as   batteries. 

 

3. Operators   must   ensure   that   interconnecting   cables   are   correctly   rated   to   carry  

the   required   load   current   and   adequately   insulated   to   prevent   the   possibility   of  
electric   shock. 

 

4. When   in   use   the   load   bank   should   be   cordoned   off   using   safety   barriers. 

 

5. The   load   bank   should   only   be   operated   in   an   area   with   adequate   ventilation. 

 

6. Care   should   be   taken   as   the   exhaust   air   outlet   will   be   hot. 

 

7. Cables   must   be   positioned   away   from   the   air   exhaust 

 

8. During   operation   the   load   bank   should   not   be   covered   or   positioned   to   restrict  

air   flow 

 

9. Caution   –   some   metal   surfaces   will   be   hot   during   operation 

 

10.At   the   end   of   any   test   the   fan   should   be   kept   running   for   10   minutes   on   no   load  

to   remove   the   residual   heat   from   the   load   bank   case. 

 

 

 

fig   2:   photo   shows   the   front   of   a   typical   HAC-PX   series   load   bank 

 

 

4  

 

Summary of Contents for HAC415-120PX

Page 1: ...OMHAC415 120PX OPERATING MANUAL for AC LOAD BANK type HAC415 120PX issue 1 Serial No M37091 1...

Page 2: ...he information contained in this document is considered correct at the time of printing and given in good faith Hillstone Products bears no responsibility for the accuracy of the data given or any res...

Page 3: ...controller The load bank is force cooled by a three phase powered cooling fan which together with the controls are supplied from the test source Safety features include internal fuse protection fan m...

Page 4: ...possibility of electric shock 4 When in use the load bank should be cordoned off using safety barriers 5 The load bank should only be operated in an area with adequate ventilation 6 Care should be tak...

Page 5: ...aximum operating voltage D Check all panel mounted ON OFF switches are in the OFF position E Connect the handheld controller to the load bank via the CAN socket F If multiple load banks are to be used...

Page 6: ...colour coding required for load bank connections H An undrilled gland plate is provided at the front of the load bank for cable entry I Connect all test cables to the load bank see fig 5 J The load co...

Page 7: ...Ensure the fan rotates in the correct direction with exhaust air being expelled from the exhaust grill there is also an indication arrow positioned above the fan which shows the direction the blades s...

Page 8: ...ach press of the UP button will increase the load of each load bank by approximately 12kW up to a maximum of 120kW 3 By pressing the DOWN button the load will decrease on each load bank by approximate...

Page 9: ...ambient temperature 10 to 45 deg C Master PCB n a Relay PCB HP FETDRV 2 ISS2 PSU PCB n a Data Log PCB n a Operating ambient temperature 0 to 40 deg C Storage ambient temperature 0 to 80 deg C Lifting...

Page 10: ...lem areas as follows FAN COOLING NOT OPERATIONAL Check the power source is available Check the interconnecting cable connections Check the fan is running in the correct direction Check the fan motor o...

Page 11: ...tity supplied 1 Date of manufacture 7th July Note This document certifies that the whole of the items detailed above have been manufactured tested and inspected and unless otherwise stated conform in...