LED Descriptions
86/154
PC Cards cifX PC/104 | Installation, Operation and Hardware Description
DOC120206UM42EN | Revision 42 | English | 2014-12 | Released | Public
© Hilscher, 2008-2014
8.23 CC-Link Slave
The subsequent table describes the meaning of the LEDs for the PC card
cifX CC-Link Slave when the firmware of the CC-Link Slave protocol is
loaded to the device.
LED
Color
State
Meaning
LED green
(off)
Off
1. Before participating in the network
2. Unable to detect carrier
3. Timeout
4. Resetting hardware
L RUN
(green)
On
Receive both refresh and polling signals or just the refresh signal normally,
after participating in the network.
LED green
(off)
Off
1. Normal communication
2. Resetting hardware
(red)
Blinking
The switch setting has been changed from the setting at the reset
cancellation (blinks for 0.4 sec.).
L ERR
(red)
On
1. CRC error
2. Address parameter error (0, 65 or greater is set including the number of
occupied stations)
3. Baud rate switch setting error during cancellation of reset (5 or greater)
Table 65: LEDs CC-Link Slave