Configuring gateway
51/98
SmartWire-DT Gateway | EU5C-SWD-ETHERCAT
DOC140901UM01EN | Revision 1 | English | 2015-03 | Released | Public
© Hilscher 2015
5. Testing cyclic data exchange with SmartWire slaves.
In the navigation tree of the TwinCAT System Manager, click on the
plus symbol in front of the gateway element
Box [x]
(EU5C-SWD-
ETHERCAT)
to expand the tree structure.
The SmartWire slaves connected to the gateway are being displayed in
the navigation tree below the gateway as
Module 1, Module 2
etc.
Figure 22: EU5C-SWD-ETHERCAT Gateway process data (1)
Select the gateway in the navigation tree, then open the
Online
tab in
the main window.
When
Free Run
mode is active, the
Current State
field in the
State
Machine
area displays
OP
state (operational). The lower area of the
main window shows the I/O data of the SmartWire slaves.
Create output data at one of the SmartWire slaves. In this example, the
switch of a device connected to the
DIL-SWD-32-001
slave (Module 1)
is being toggled.
This event is indicated by a changed value in the
Online
field of the first
IB0
object in the lower area of the main window:
Figure 23: EU5C-SWD-ETHERCAT Gateway process data (2)