Parameterization
56/98
SmartWire-DT Gateway | EU5C-SWD-ETHERCAT
DOC140901UM01EN | Revision 1 | English | 2015-03 | Released | Public
© Hilscher 2015
The
Edit
CANopen Startup Entry
dialog window
opens. The
Data
(hexbin)
field displays the preset hexadecimal value of the byte
configuring this parameter. In case of the baud rate, this is the value
7D
00
(the
00
byte is a reserved byte):
Figure 27: Editing parameters of SWD Coordinator (2)
In the
Data (hexbin)
field, enter the new hexadecimal value of the
parameter. Omit the
0x
prefix; i. e. enter the value
0xFA
simply as
string
FA
. You can delete the reserved second byte (i. e. the
00
byte).
Note:
Entering the value
FA
(decimal =
250
) in this example causes the
Coordinator (i. e. the gateway) to run the SmartWire-DT network with a
250
kBaud/s rate.
What value has to be entered for other parameters is shown in table
Parameter settings of SWD Coordinator
on page 54.
Take over the new value by clicking the