Parameterization
66/98
SmartWire-DT Gateway | EU5C-SWD-ETHERCAT
DOC140901UM01EN | Revision 1 | English | 2015-03 | Released | Public
© Hilscher 2015
9.3.3
Configuring device parameters (sensor parameters of I/O
modules)
9.3.3.1
Overview
For some SmartWire-DT devices, individual device parameters can be
configured.
Configurable parameters of the SmartWire-DT devices are described in
the manual
SmartWire-DT Units
, Doc ID MN05006001Z-EN, which is
stored on the product DVD in the directory
Documentation\english\3.SmartWire-DT\SmartWire-DT –
Units\MN05006001Z_EN.pdf
This section describes how to
configure sensor type, refresh rate and
averaging of the inputs/outputs modules
EU5E-SWD-4AX
,
EU5E-SWD-
2A2A
and
EU5E-SWD-4PT
by editing their
Parameters
element (sub index
22)
in TwinCAT.
Please note that this section is of exemplary nature. You always have to
look up the definite bit assignment of the parameter byte of individual
devices in the latest documentation of the device’s manufacturer.
The subsequent tables show the bit assignments of the
Parameters
bytes
of the SmartWire-DT devices
EU5E-SWD-4AX
,
EU5E-SWD-2A2A
and
EU5E-SWD-4PT
:
EU5E-SWD-4AX
Byte value
Bit
Parameter
(function)
Configuration
Dez
Hex
FALSE
(0)
: Voltage (default)
0 0x00
0
Sensor selector
Input 1
TRUE
(1)
: Current
1 0x01
FALSE
(0)
: Voltage (default)
0 0x00
1
Sensor selector
Input 2
TRUE
(1)
: Current
2 0x02
FALSE
(0)
: Voltage (default)
0 0x00
2
Sensor selector
Input 3
TRUE
(1)
: Current
4 0x04
FALSE
(0)
: Voltage (default)
0 0x00
3
Sensor selector
Input 4
TRUE
(1)
: Current
8 0x08
Bit 5
Bit 4
Milli
seconds
FALSE
(0)
FALSE
(0)
20 ms
0 0x00
FALSE
(0)
TRUE
(1)
100 ms
(default)
16 0x10
TRUE
(1)
FALSE
(0)
200 ms
32 0x20
4 - 5 Reading refresh rate
TRUE
(1)
TRUE
(1)
500 ms
48 0x30
FALSE
(0)
: off
0 0x00
6
Mean value
(averaging)
TRUE
(1)
: on (default)
64 0x40
7 Reserved
FALSE
(0)
0 0x00
Table 15: Bit assignment of parameter byte of EU5E-SWD-4AX