EU5E-SWD-4PT
Byte 1:
Byte value
Bit
Parameter
Configuration
Dez
Hex
Bit 1
Bit 0
Sensor type
FALSE
(0)
FALSE
(0)
Not used (default)
0 0x00
FALSE
(0)
TRUE
(1)
PT100
1 0x01
TRUE
(1)
FALSE
(0)
PT1000
2 0x02
0 - 1 Sensor
selection
Input 1
TRUE
(1)
TRUE
(1)
NI1000
3 0x03
Bit 3
Bit 2
Sensor type
FALSE
(0)
FALSE
(0)
Not used (default)
0 0x00
FALSE
(0)
TRUE
(1)
PT100
4 0x04
TRUE
(1)
FALSE
(0)
PT1000
8 0x08
2 - 3 Sensor
selection
Input 2
TRUE
(1)
TRUE
(1)
NI1000
12 0x0C
Bit 5
Bit 4
Sensor type
FALSE
(0)
FALSE
(0)
Not used (default)
0 0x00
FALSE
(0)
TRUE
(1)
PT100
16 0x10
TRUE
(1)
FALSE
(0)
PT1000
32 0x20
4 - 5 Sensor
selection
Input 3
TRUE
(1)
TRUE
(1)
NI1000
48 0x30
Bit 7
Bit 6
Sensor type
FALSE
(0)
FALSE
(0)
Not used (default)
0 0x00
FALSE
(0)
TRUE
(1)
PT100
64 0x40
TRUE
(1)
FALSE
(0)
PT1000
128 0x80
6 - 7 Sensor
selection
Input 4
TRUE
(1)
TRUE
(1)
NI1000
192 0xC0
Table 17: Bit assignment of parameter byte 1 of EU5E-SWD-4PT
Byte 2:
Byte value
Bit
Parameter
Configuration
Dez
Hex
Bit 1
Bit 0
Unit
FALSE
(0)
FALSE
(0)
Degrees Celsius
(default)
0 0x00
FALSE
(0)
TRUE
(1)
Degrees Fahrenheit
1 0x01
0 - 1 Measurement
display
TRUE
(1)
FALSE
(0)
Binary value
2 0x02
Bit 3
Bit 2
Rate
FALSE
(0)
FALSE
(0)
0.25 s (default)
0 0x00
FALSE
(0)
TRUE
(1)
1 s
4 0x04
TRUE
(1)
FALSE
(0)
2.5 s
8 0x08
2 - 3 Reading
refresh rate
TRUE
(1)
TRUE
(1)
10 s
12 0x0C
4 Reserved
FALSE
(0)
0 0x00
5 Reserved
FALSE
(0)
0 0x00
6 Reserved
FALSE
(0)
0 0x00
7 Reserved
FALSE
(0)
0 0x00
Table 18: Bit assignment of parameter byte 2 of EU5E-SWD-4PT