Parameterization
69/98
SmartWire-DT Gateway | EU5C-SWD-ETHERCAT
DOC140901UM01EN | Revision 1 | English | 2015-03 | Released | Public
© Hilscher 2015
The following exemplary step-by-step instructions show how to change the
parameter “Reading refresh rate” of the
EU5E-SWD-4AX
device from
100
ms
(default) to
200
ms
.
9.3.3.2
Prerequisites
PC with installed TwinCAT System Manager V2.11 and Ethernet adapter
You have created a valid project configuration (see
Configuring gateway
in TwinCAT
section on page 45) and have opened the project
configuration in the TwinCAT System Manager
The project features the
EU5E-SWD-4AX
SmartWire-DT I/O module
9.3.3.3
Step-by-step instructions
In the navigation tree of the TwinCAT System Manager, select the
gateway, then open the
Startup
tab in the main window.
The configuration elements are listed in the
Startup
tab:
Figure 34: Editing device parameters of SWD device (1)
Search the list for the SmartWire-DT device and the
Parameters
element that you want to edit. An
Parameters
element can be
recognized by the index
0x8XXX:22
and the
Parameters [device
name]
entry in the
Comment
column.