Parameterization
70/98
SmartWire-DT Gateway | EU5C-SWD-ETHERCAT
DOC140901UM01EN | Revision 1 | English | 2015-03 | Released | Public
© Hilscher 2015
Select the
Parameters
element, then click
Edit
button (or double-click
the element).
The
Edit
CANopen Startup Entry
dialog window
opens. The
Data
(hexbin)
field displays the preset hexadecimal value of the parameter
byte. In case of the
EU5E-SWD-4AX
device, this is the value
02 50
:
Figure 35: Editing device parameters of SWD device (2)
Important:
Please note that the first byte in the
Data (hexbin)
field (in this
example
02
) is the “length byte” denoting the total number of bytes
contained in the Parameters element. This first length byte must not be
changed.
In case of the devices
EU5E-SWD-4AX
and
EU5E-SWD-2A2A
, the
Parameters element consists of two bytes of which you are allowed to
change only the second byte. In case of the
EU5E-SWD-4PT
device, the
Parameters element consists of three bytes of which you are allowed to
change only the last two bytes.
In the
Data (hexbin)
field, change the value of the second byte. Omit
the
0x
prefix; i. e. enter the value
0x60
simply as string
60
.
Note:
The
Parameters
can only be configured by entering hexadecimal
byte values. For changing the parameters, you therefore have to
recalculate a new byte value. The outcome of this calculation depends on
the parameter bits you are changing and on the default settings of the
device. Entering the value
60
in this example changes the “Reading
refresh rate” of the device from
100
ms
(default) to
200
ms
.
For an example of how to calculate the parameters byte, see
Example of
calculating the parameters byte
section on page 71.
Take over the new value by clicking the
OK
button.